P2101[3] Stop reaction value
Min: 0 Def: 0 Max: 4
Level 3
Details: Sets drive stop reaction values for fault selected by P2100 (alarm number stop reaction).
This indexed parameter specifies the special reaction to the faults/warnings defined in P2100 indices 0 to 2.
Enum: 0=No reaction, no display
1=OFF1 stop reaction
2=OFF2 stop reaction
3=OFF3 stop reaction
4=No reaction warning only
Note: Settings 0 to 3 only are available for fault codes
Settings 0 and 4 only are available for warnings
Index 0 (P2101) refers to fault/warning in index 0 (P2100)
r2110[4] Warning number
Min: - Def: - Max: -
Level 2
Details Displays warning information.
A maximum of two active warnings (indices 0 and 1) and 2 historical warnings (indices 2 and 3) may be viewed.
Index: r2110[0] : Recent Warnings --, warning 1
r2110[1] : Recent Warnings --, warning 2
r2110[2] : Recent Warnings -1, warning 3
r2110[3] : Recent Warnings -1, warning 4
Note: The keypad will flash while a warning is active. The LEDs indicate the warning status in this case.
If an AOP is in use, the display will show number and text of the active warning.
Indices 0 and 1 are not stored.
P2111 Total number of warnings
Min: 0 Def: 0 Max: 4
Level 3
Details: Displays number of warning (up to 4) since last reset. Set to 0 to reset the warning history.
r2114[2] Run time counter
Min: - Def: - Max: -
Level 3
Details: Displays run time counter. See P-948 (fault time).
P2115[3] AOP real time clock
Min: 0 Def: 0 Max: 65535
Level 3
Details: Displays run time counter. See P-948 (fault time).
P2181 Belt failure detection mode
Min: 0 Def: 0 Max: 6
Level 2