Operating Instructions

Appendix A: Parameter Reference List
Siemens Building Technologies, Inc. 171
P2376 Delay override
Min: 0.0 Def: 25.0 Max: 200.0
Level 2
Details: Error as a percentage of setpoint that if exceeded will begin staging without delay.
P2377 Delay override lockout timer
Min: 0 Def: 30 Max: 650
Level 2
Details: Time for which delay override is prevented after a motor has been staged or destaged.
P2378 Staging frequency f, %fMax
Min: 0.0 Def: 50.0 Max: 120.0
Level 2
Details: The frequency as a percentage of fMax at which anexternal motor will be started or stopped
r2379 CO/BO: Status of motor staging
Min: - Def: - Max: -
Level 2
Bit Fields:
Bit00 Start motor 1 0 YES, 1 NO
Bit01 Start motor 2 0 YES, 1 NO
Bit02 Start motor 3 0 YES, 1 NO
P2380[3] Motor hours run
Min: 0 Def: 0 Max: 100000
Level 2
Index: P2380[0] : Motor 1 hrs run P2380[1] : Motor 2 hrs run P2380[2] : Motor 3 hrs run
Note: To reset the running hours, set the value to zero, any other value is ignored.
P2390 Hibernation frequency
Min: 0 Def: 0 Max: 650.00
Level 3
Details: Hibernation frequency setpoint (frequency the motor output will turn off).
P2391 Hibernation timer
Min: 0 Def: 0 Max: 650.00
Level 3
Details: Hibernation restart frequency (frequency the motor output will turn on).
P2392 Restart frequency
Min: 0 Def: 0 Max: 650.00
Level 3
Details: Hibernation restart frequency (frequency the motor output will turn on).
P3900 End of quick commissioning
Min: 0 Def: 0 Max: 3
Level 1