Details: Performs calculations necessary for optimized motor operation.
After completion of calculation, P3900 and P0010 (parameter groups for commissioning) are automatically reset
to their original value 0.
Enum: 0=No quick commissioning
1=Start quick commissioning with factory reset
2=Start quick commissioning
3=Start quick commissioning only for motor data
Dependency: Changeable only when P0010=1 (quick commissioning)
Note: When setting 1 is selected, only the parameter settings carried out via the commissioning menu "Quick
commissioning", are retained; all other parameter changes, including the I/O settings, are lost. Motor calculations
are also performed.
When setting 2 is selected, only those parameters, which depend on the parameters in the commissioning menu
"Quick commissioning" (P0010=1) are calculated. The I/O settings are also reset to default and the motor
calculations performed.
When setting 3 is selected, only the motor and controller calculations are performed. Exiting quick commissioning
with this setting saves time (for example, if only motor rating plate data have been changed).
Calculates a variety of motor parameters, overwriting previous values. These include P0344 (Level 3, motor
weight), P0350 (Level 3, demagnetization time), P2000 (reference frequency), P2002 (Level 3, reference current).