Operating Instructions
SED2 Operation & Maintenance Manual Addendum
176 Siemens Building Technologies, Inc.
L1
L2
L3
PE
BMS
SED2
wvu
5192Z04en
Min. 16 mm²
(4 AWG)...
compensating cable
Install all cables on the
same side of the plate
Min.200 mm
(7.8 inches)....
between
control cables,
motor cables and
mains cables
Motor cable
Mains power supply
Min.10 mm² (6 AWG)...
PE: min.10 mm² (6 AWG)...
Remove cable
insulation
Control cables
Grounding rail
Motor
Figure 41. Routing Control, Mains, and Motor Cables.