Operating Instructions

Appendix D: Programming
Siemens Building Technologies, Inc. 185
P1264, Bypass time
Time delay before a request to switch to mains is executed (Figure 49).
Setting range: 0 to 300 second
Recommended setting: 1 second (default).
Complete parameter setting by changing over to automatic control.
P1264 P1262 P1262P1263
t (s)
(Bypass request)
Bypass contactor
VSD contactor
Alarm
5192D03en
Figure 49. Bypass Timing Diagram.