Operating Instructions

Chapter 5 – Commissioning
Siemens Building Technologies, Inc. 29
Default Commissioning Settings
Default settings for operation with the BOP are as follows:
Parameter Description Default Value for North America
(Europe)
P0100 For USA or Europe
power setting
0 = 50 Hz, kW (Europe), factory default
1 = 60 Hz, hp (North America)
2 = 60 Hz, kW (North America)
The setting of Motor Frequency & Units of Measurement DIP
switch 2 overwrites P0100 settings 0 and 1. See the DIP Switch
Settings section for details.
NOTES:
1. Stop the drive (that is, disable all pulses) before changing
this parameter.
2. Commissioning Parameter Filter P0010=1 (quick
commissioning mode) enables changes via P0100.
3. Changing P0100 resets all rated motor parameters as well
as other parameters that depend on the rated motor
parameters (see P0340, Calculation of Motor Parameters).
P0307 Nominal motor
power
Value in hp or kW depending on setting of P0100.
Default for P0307 is 0.75.
P0010=1 (commissioning mode) enables changes via P0307.
P0308 or
P0309
Rated motor cosPhi
(P0308) or
Rated motor
efficiency (P0309)
P0308 displays when P0100=0 or 2 and P0307 motor power is
entered in kW. Default for P0308 is 0.000.
P0309 displays when P0100=1 and P0307 motor power is
entered in hp. Default for P0309 is 0.0.
NOTE: P0309=100% corresponds to superconducting.
P0010=1 (commissioning mode) enables changes via P0308 or
P0309.
P0310 Nominal motor
frequency
60 Hz or 50 Hz (default). Pole pair number is recalculated
automatically if the parameter is changed.
P0010=1 (commissioning mode) enables changes via P0310.
P0311 Nominal motor
speed
1680 (1395) U/min (depends on model); default for P0311 is 0.
A setting of 0 causes an internal calculation of the value.
Vector control and V/f control with speed controller require this
value. Slip compensation in V/f control requires this value for
correct operation. Pole pair number is recalculated automatically
if the parameter is changed.
P0010=1 (commissioning mode) enables changes via P0311.
P0640 Motor overload
factor, %
Limited to a maximum inverter current or up to 400% of rated
motor current (P0305), whichever is lower.
Default for P0640 is 150.0.
Continued