Operating Instructions
Chapter 5 – Commissioning
Siemens Building Technologies, Inc. 31
It is important to use parameter P0010 to commission the SED2, and P0003 to select the
number of accessible parameters. Parameter P0010 allows you to select a group of
parameters that can be used for quick commissioning. These include parameters for the
motor data (Figure 22), and for the motor ramp-up and ramp-down settings.
At the end of the quick commissioning procedure, select P3900. When set to 1, this
parameter performs the necessary motor calculations and sets all remaining parameters
(those not included under P0010 = 1) to the default values, including P0010=0 (if P0010=1,
the VFD cannot start). This process is only possible in the “quick commissioning” mode.
Motor Data for Commissioning Parameters
Motor parameters can only be modified if Commissioning Parameter Filter P0010=1 (for
quick commissioning). The motor control functions of the BOP are disabled by default. Set
Selection of Command Source parameter P0700[0]=1 (for BOP) and Selection of Frequency
Setpoint P1000[0]=1 (for motor potentiometer setpoint) to enable motor control using the
BOP.
If the BOP was configured for I/O control (P0700[0] is set to 1), the motor stops when the
BOP is removed.
P0308 P0310 P0304
SIEMENS
PE 21 PLUS TM PREMIUM EFFICIENCY
TEFC
3 PH
60 Hz
Type :
HP :
Volts :
Amps :
RPM :
NEMA nom Eff :
Frame :
Sh end brg :
Opp end brg :
Part No :
RGZZESD
3
230YY/460Y
7,8 / 3,9
1740
87,5 %
182 T
30BC02JP3
30BC02JP3
1MJP1824YP60
LR 39020
Rating :
Ins Class :
Serv Factor :
Amb Temp :
Temp Rise :
NEMA design :
KVA Code :
Weight :
Serial No : M
Cont
F
1,0
40 C
Class B
B
K
95 lbs
00T0194 CE 18
LOW VOLTAGE
CONNECTION
HIGH VOLTAGE
CONNECTION
LINE
LINE
5
4 6
87 9
21 3
54 6
87 9
21 3
o
P0304
P0305
P0307
P0310
P0311
P0309
Figure 22. Motor Nameplate Data for Commissioning Parameters.