Operating Instructions
SED2 VFD Operation & Maintenance Manual
34 Siemens Building Technologies, Inc.
Step Action Resulting display
6
Press to confirm and save the value.
7
Press to return to P0010.
Hz
P(1)
2
8
Press
to access the parameter values level.
Hz
P(1)
9
Press
to restore the value of Commissioning Parameter Filter
P0010 to 0 (ready).
Hz
P(1)
10
Press
to confirm and save the value, and to exit from the
parameter values level.
Hz
P(1)
2
11
Press until r0000 displays or press
to return to r0000.
12
Press
to revert to the standard motor display (as defined by
the customer).
NOTE: “Busy Signal” — While changing parameters, the BOP can display for a
maximum of 5 seconds. This means that the SED2 is busy with higher-priority
activities.
Changing Individual Parameter Digits
To quickly change the value of a parameter, modify the individual digits in the display as
follows:
1. Verify that you are at the parameter modification level (See the Setting Parameters with a
BOP or AOP section in this manual).
2. Press
. The right-most digit starts to flash.
3. Modify the value of this digit with the
and buttons.
4. Press
again. The next digit starts flashing.
5. Repeat steps 2 through 4 until the required value displays.
6. Press
to exit the parameter modification level.