Operating Instructions
Chapter 6 – Programming
Siemens Building Technologies, Inc. 49
Index:
P0761[0]: IN000=Analog input 1.
P0761[1]: IN001=Analog input 2.
Analog Outputs
SED2 converts status variables such as output frequency, motor voltage, or present motor
current via D/A converters (DAC) within a scaleable range. The analog outputs then display
their values
NOTE: For accurate and consistent performance of SED2 analog outputs, if you are not
connecting a NI 1000 sensor then terminals 10 and 4 (NI 1000) must connect to
terminal 2 (0V).
AOUT1
D / A
V: 0 - 10 V
2 - 10 V
I: 0 - 20mA
4 - 20mA
13
12
AOUT2
D / A
V: 0 - 10 V
2 - 10 V
I: 0 - 20mA
4 - 20mA
27
26
Analog Output
r0770 - P0781
5192B03en
Figure 30. SED2 Analog Outputs 1 and 2.
Parameter Settings for AOUT1 and AOUT2 (Commissioning)
P0773
1 + 2
r0774
1 + 2
P0781
1 + 2
P0771
1 + 2
P0780
P0779
P0778
P0777
P0776
Function
SCAL
Output
Deadband
5192Z27en
Output:
Current or
voltage
P0771, Physical status variable
Defines the physical status variable to display as an analog signal. Possible settings: