Chapter 6 – Programming
Siemens Building Technologies, Inc. 53
Index:
P0700[0]: IN000 (AUTO)=1st command data set (CDS).
P0700[1]: IN001 (HAND)=2nd command data set (CDS).
Start Motor
Default setting: Terminal 5 (DIN 1, high).
Additional settings: See Selection of Command Source parameter P0700 and Function of
Digital Inputs 1 to 8 parameters P0701 through P0708.
NOTE: The ramp-up and ramp-down smoothing times influence the motor's start and
stop behavior. For more information, see Ramp-Up Time parameter P1120 and
Ramp-Down Time parameter P1121 in the Appendix A: Parameter Reference List
section of this document.
Stop Motor
There are several ways to stop the motor:
Default setting:
OFF1 Terminal 5 (DIN 1, low).
OFF2 OFF button on BOP/AOP; sustained pressing of the OFF button (two seconds) or
repeated pressing of the button (in case of default settings not possible without BOP/AOP).
Additional settings: See Selection of Command Source parameter P0700 and Function of
Digital Inputs 1 to 8 parameters P0701 through P0708.
Reversal of the Motor’s Direction of Rotation
Default setting: Terminal 6 (DIN 2, high).
Additional settings: See Selection of Command Source parameter P0700 and Function of
Digital Inputs 1 to 8 parameters P0701 through P0708.
OFF Functions
OFF1
This command (by eliminating the ON command) stops the SED2 within the selected ramp-
down time.
See Ramp-Down Time parameter P1121 to change the ramp-down time.