Operating Instructions

Chapter 7 – Troubleshooting
Siemens Building Technologies, Inc. 69
Fault Codes
Error Cause Diagnosis/Remedy Reaction
F0001,
Overcurrent
Motor power (P0307) is
greater than SED2
power (P0206).
Motor lead short circuit.
Earth faults.
Check the following:
Motor power (P0307) SED2 power
(P0206).
Cable length limits must not be
exceeded.
Motor cable and motor must not
have short circuits or earth faults.
Motor parameters must match the
motor in use.
Value of stator resistance (P0350)
must be correct.
The motor must not be obstructed or
overloaded.
Increase ramp-up time.
Reduce boost level.
Off2
F0002,
Overvoltage
DC link voltage (r0026)
exceeds trip level.
Overvoltage can be
caused either by too
high main supply
voltage or if motor is in
regenerative mode.
Regenerative mode can
be caused by fast ramp
downs or if the motor is
driven from an active
load.
Check the following:
The supply voltage must lie within
the limits indicated on the rating
plate.
The DC link voltage controller must
be enabled (P1240) and
parameterized correctly.
The ramp-down time (P1121) must
match the inertia of load.
The required braking power must lie
within the specified limits.
NOTE: Higher inertia requires long ramp-
down times; otherwise, apply braking resistor.
Off2
F0003,
Undervoltage
Mains supply failed.
Shock load outside the
specified limits.
Check the following:
The supply voltage must lie within
the limits indicated on the rating
plate.
The supply voltage must not be
susceptible to temporary failures or
voltage reductions outside tolerance.
Off2