Operating Instructions

SED2 VFD Operation & Maintenance Manual
70 Siemens Building Technologies, Inc.
Error Cause Diagnosis/Remedy Reaction
F0004, SED2
Overtemperature
Ventilation is
inadequate.
The fan is inoperative.
The ambient
temperature is too high.
Check the following:
The fan must turn when the SED2 is
running.
The pulse frequency must be set to
a lower value.
The ambient temperature could be
higher than specified for the SED2.
Off2
F0005, SED2 I2T
The SED2 is
overloaded.
The duty cycle is
outside the tolerance.
The motor power
(P0307) exceeds the
SED2 power (P0206).
Check the following:
The load cycle must lie within the
limits specified.
2Motor power (P0307) SED2 power
(P0206).
Off2
F0011, Motor
overtemperature
The motor is overloaded
Make sure that the load duty cycle (temporary
overload) lies within the limits specified.
Off1
F0012, SED2
temperature
signal lost
Wire breakage of the
SED2 temperature
sensor (heat sink).
Off2
F0015, Motor
temperature
signal lost
Breakage or short-
circuit of the motor
temperature sensor.
If a signal loss is
detected, temperature
monitoring switches to
monitoring the thermic
motor image.
Off2
F0020, 1 phase
for mains supply
missing
One of the 3 phases for
the mains supply
voltage is missing.
Check the wiring of the 3 phases at the
supply voltage input of the SED2.
Off2
F0021, ground
fault
The ground fault occurs
if the sum of the phase
currents is higher than
5% of the nominal
SED2 current.
NOTE: This error message
occurs on SED2 drives with three
current sensors; that is, for SED2
drives of frame sizes D to F.
Off2