Chapter 7 – Troubleshooting
Siemens Building Technologies, Inc. 75
Reading Faults
OK FAULT (r0052, bit 3) is a read-only fault status point (0=OK, 1=Fault).
LAST FAULT (r0947(0)) shows the code for the most recent fault.
Resetting Faults
Press to reset a fault condition.
OK FAULT (r0052, bit 3) is a read-only fault status point (0=OK, 1=Fault). It can be acknowledged
with FAULT ACK (r0054, bit 7). Setting FAULT ACK (r0054, bit 7) resets the fault (1=Reset Fault).
NOTE: It is possible that motor performance may be affected at low frequencies if parameter P1310
falls under 50% (default value).
Warning Messages
Error Cause Diagnosis and Remedy Reaction
A0501, Current
limit
Motor power > SED2
power.
Motor cables are too
long.
Ground faults.
Check the following:
Motor power (P0307) SED2 power
(P0206).
Cable length limits must not be
exceeded.
Motor cable and motor must not
have short circuits or earth faults.
Motor parameters must match the
motor in use.
Value of stator resistance (P0350)
must be correct.
The motor must not be obstructed or
overloaded.
Increase ramp-up time.
Reduce boost level.
--
A0502,
Overvoltage limit
The overvoltage limit is
reached.
This warning may appear on
ramp-down if the DC link is
disabled (P1240 = 0).
If this warning is displayed permanently,
check the drive input voltage or extend the
ramp-down time for the drive.
--