Specifications

SED2 VFD Startup, Operation, and Maintenance Manual
90 Siemens Building Technologies, Inc.
Error Cause Diagnosis/Remedy
Drive
Reaction
F0080,
Analog input
signal lost
Broken wire at analog
input.
Signal level outside
defined limits.
— Off2
F0085,
External fault
External fault triggered via
input terminals.
Disable input terminals for fault
trigger, or eliminate external fault.
Check if digital input is set to ON.
Off2
F0101, Stack
overflow
Software or processor error.
Run self-test routines. Off2
F0221, PID
feedback
below min.
value
PID feedback below
minimum value of P2268,
minimum value for PID
feedback.
Change value of P2268.
Adjust feedback amplification.
Off2
F0222 PID feedback above
maximum value.
PID feedback, maximum value of
P2267 (maximum value for PID
feedback).
Adjust feedback amplification.
Off2
F0450, BIST
tests failure
Alarm value:
1. Some power section
tests have failed.
2. Some control module
tests have failed.
4. Some functional tests
have failed.
8. Some I/O module tests
have failed.
16. Internal RAM failed on
power-up check.
SED2 may run, but some
functions do not work properly.
Replace the SED2.
Off2