Specifications
Mechanical Installation
Siemens Building Technologies, Inc. 19
Dimensions and Mounting for IP54,
NEMA Type 12 SED2s
Overall Dimensions and Mounting
Specifications
Table 4. Overall Dimensions and Mounting Clearances for IP54, NEMA
Type 12 SED2. Dimensions in Inches (Millimeters).
Overall Dimensions Mounting Clearance
Frame
Size
Height
Width
Depth Top Bottom
Sides
Mounting
Specification
Tightening
Torque
lb-in (Nm)
Weight
lb (kg)
B
15.2
(385)
10.6
(270)
10.6
(268)
5.9
(150)
5.9
(150)
3.9
(100)
4 x M6 Bolts,
Nuts, and
Washers
44
(5)
22
(10)
C
23.9
(606)
13.8
(350)
11.2
(284)
5.9
(150)
5.9
(150)
3.9
(100)
4 x M6 Bolts,
Nuts, and
Washers
44
(5)
42
(19)
D
27.0
(685)
14.2
(360)
13.9
(353)
7.9
(200)
7.9
(200)
5.9
(150)
4 x M8 Bolts,
Nuts, and
Washers
115
(13)
77
(35)
E
34.8
(885)
14.2
(360)
17.8
(453)
7.9
(200)
7.9
(200)
5.9
(150)
4 x M8 Bolts,
Nuts, and
Washers
115
(13)
105
(48)
F
45.3
(1150)
17.7
(450)
18.6
(473)
11.8
(300)
9.8
(250)
5.9
(150)
4 x M8 Bolts,
Nuts, and
Washers
177
(20)
178
(81)