Specifications

Electrical Installation
Siemens Building Technologies, Inc. 37
Input Power Connection
DANGER:
As supplied, the SED2 must be grounded (per IEC
536, Class 1, NEC and other relevant industry
standards). Extremely hazardous conditions can occur if
the SED2 is not correctly grounded.
Use only permanently wired input power connections.
Only hard-
wired input power connections are permissible.
Use Class 1 60/75° copper wire only.
The cross-section of the ground-bonding conductor must
be at least equal to the input power cables.
The following terminals can carry hazardous voltages
even when the SED2 is not running:
Input power terminals: L1, L2, L3
Motor terminals: U, V, W
Link terminals: DC-, DC+/B+, DC/R+, B- (not for
customer use)
Connect input power to SED2 terminals L1, L2, and L3 (Figures 19
through 22).