Specifications
SED2 VFD Startup, Operation, and Maintenance Manual
56 Siemens Building Technologies, Inc.
Motor Nameplate Data for Parameter
Settings
You can modify motor data via the parameter settings only if
Commissioning Parameter Filter P0010=1, for the quick commissioning
procedure.
Motor control via the BOP is enabled in Hand mode by default. To
enable motor control via the BOP during the quick commissioning
procedure, set Selection of Command Source parameter P0700[0]=1 (for
BOP) and Selection of Frequency Setpoint P1000[0]=1 (for motor
potentiometer setpoint).
If the BOP is configured for control (P0700[0]=1 for BOP), the motor
stops when the BOP is removed.
SIEMENS
PE 21 PLUS
TM
PREMIUM EFFICIENCY
TEFC
3 PH
60 Hz
Type :
HP :
Volts :
Amps :
RPM :
NEMA nom Eff :
Frame :
Sh end brg :
Opp end brg :
Part No :
RGZZESD
3
230YY/460Y
7,8 / 3,9
1740
87,5 %
182 T
30BC02JP3
30BC02JP3
1MJP1824YP60
LR 39020
Rating :
Ins Class :
Serv Factor :
Amb Temp :
Temp Rise :
NEMA design :
KVA Code :
Weight :
Serial No : M
Cont
F
1,0
40 C
Class B
B
K
95 lbs
00T0194 CE 18
LOW VOLTAGE
CONNECTION
HIGH VOLTAGE
CONNECTION
LINE
LINE
5
4 6
87 9
21 3
54 6
87 9
21 3
o
P0304
P0305
P0307
P0310
P0311
P0309
VFD0032R1
Figure 39. Motor Nameplate Data for Commissioning Parameters.