Specifications

Commissioning
Siemens Building Technologies, Inc. 61
Quick Commissioning Procedure
Parameter P0010 is the Commissioning Parameter Filter. It allows you to
select a group of parameters that can be used for quick commissioning,
including motor data (Figure 39), and motor ramp-up and ramp-down
settings.
It is important to use parameter P0010 to commission the SED2, P0003
to select the access level for using parameters, and P0004 to filter the
parameters according to their functionality. When Commissioning
Parameter Filter P0010=1, it initiates the quick commissioning
procedure.
It is recommended that you use the quick commissioning procedure.
However, experienced users may commission the equipment without the
P0004 filter functions.
At the end of the quick commissioning procedure, set parameter
P3900=1. This setting performs the necessary motor calculations and
sets all remaining parameters (those not included in P0010=1) to the
factory default values. If P3900 is set to a value greater than 0, P0010 is
automatically reset to 0. (If P0010=1, the SED2 cannot start.) The
process of performing motor calculations and setting all parameters to
factory default values is only possible via quick commissioning.
Parameter Description Action Setting/ Default
User Access Level
Allows you to access more
parameters.
1 = Standard
2 = Extended
3 = Expert
1. Press
to access
parameter r0000 and to
enter the SED2 parameter
mode.
2. Press
to advance to
parameter P0003.
3. Press
to access the
parameter values level.
4. Press
to advance to 3
(expert level).
5. Press
to confirm and
save the P0003=3 setting.
Setting = 3
Default = 1
P0003
NOTE:
1. Before starting quick commissioning, set P0003=3 to ensure all necessary
parameters are available during quick commissioning.