Specifications

SED2 VFD Startup, Operation, and Maintenance Manual
66 Siemens Building Technologies, Inc.
Parameter Description Action Setting/ Default
Selection of Command
Source
(Start Command)
Selects the command
source as follows:
0 = Factory default
setting
1 = BOP (keypad)
2 = Terminal digital input
4 = USS on BOP link
(AOP)
5 = USS on COM link
6 = CB (communications
board or module) on
COM link (P1/N2)
1. Press
to advance to
parameter P0700.
2. Press
to access the
parameter indexes.
3. Press
to advance to
index [0], IN000, AUTO.
4. Press
to confirm index
selection.
5. Press
to advance to 2.
6. Press to confirm and
save the setting.
Setting = 2
Default = 2
P0700[0]
**
NOTE:
Changing this parameter resets (to default) all setting on the selected item. For
example, changing from 1 to 2 resets all digital inputs to default settings.
Selection of Command
Source
(Start Command)
Selects the command
source as follows:
0 = Factory default
setting
1 = BOP (keypad)
2 = Terminal digital input
4 = USS on BOP link
(AOP)
5 = USS on COM link
6 = CB (communications
board or module) on
COM link (P1/N2)
1. Press
to advance to
index [1], IN001, HAND.
2. Press
to confirm index
selection.
3. Press
to advance to 1.
4. Press to confirm and
save the setting.
5. Press
again to return to
the parameter selection
level.
Setting = 1
Default = 1
P0700[1]
**
NOTE:
Changing this parameter resets (to default) all setting on the selected item. For
example, changing from 1 to 2 resets all digital inputs to default settings.
** Parameters have two index settings: IN000=Auto and IN001=Hand.