Specifications
SED2 VFD Startup, Operation, and Maintenance Manual
72 Siemens Building Technologies, Inc.
Automatic Restart
CAUTION:
Setting 2 through 5 can cause the motor to restart unexpectedly.
Parameter Description Action Setting/ Default
Automatic Restart
Enables SED2 restart after a
supply power break or after a
fault.
0 = Disabled
1 = Trip reset after power
on (P1211 disabled)
2 = Restart after supply
power blackout
(P1211 disabled)
3 = Restart after brownout
or fault
(P1211 enabled)
4 = Restart after supply
power brownout
(P1211 disabled)
5 = Restart after blackout
or fault
(P1211 disabled)
1. Press
to enter the
SED2 parameter mode
and to display r0000.
2. Press
to advance
to parameter P1210.
3. Press
to access the
parameter values level.
4. Press
to advance
to desired setting.
5. Press
to confirm
and save the setting.
Minimum: 0
Default: 1
Maximum: 5
Setting: 3
P1210
NOTES:
1. Auto restart requires a constant ON command (such as via a digital input).
2. P1200 flying start must be used in cases where the motor may still be
turning, such as after a brief input power break, or can be driven by the
load.
3. A supply power brownout is when the power is interrupted and reapplied
before the operator panel display has gone dark. It is a very short supply
power break where the DC link has not fully collapsed
4. A supply power blackout is when the operator panel display has gone
dark before the power is reapplied. It is a long supply power break where
the DC link has fully collapsed.