Specifications

SED2 VFD Startup, Operation, and Maintenance Manual
84 Siemens Building Technologies, Inc.
Fault Codes
Error Cause Diagnosis/Remedy
Drive
Reaction
F0001,
Overcurrent
Motor power (P0307) is
greater than SED2 power
(P0206).
Motor lead short circuit.
Ground faults.
Motor is pulling more
current than rating
because of mechanical
issues.
Motor power (P0307) SED2
power (P0206).
Cable length limits must not be
exceeded.
Short circuits or ground faults in
motor cable and motor.
Motor parameters must match
the motor in use.
Value of stator resistance
(P0350) must be correct.
Motor is obstructed or
overloaded.
Increase ramp-up time.
Reduce boost level.
Off2