Specifications

SED2 VFD Startup, Operation, and Maintenance Manual
86 Siemens Building Technologies, Inc.
Error Cause Diagnosis/Remedy
Drive
Reaction
F0004,
SED2 over-
temperature
Ventilation is inadequate.
Fan is inoperative.
The ambient temperature
is too high.
Fan must turn when the SED2 is
running.
Pulse frequency must be set to a
lower value.
Ambient temperature could be
higher than specified for the
SED2.
Off2
F0005,
SED2 I
2
t
The SED2 is overloaded.
Duty cycle is outside the
tolerance.
Motor power (P0307)
exceeds the SED2 power
(P0206).
Load cycle must lie within the
limits specified.
Motor power (P0307) SED2
power (P0206).
Off2
F0011, Motor
over-
temperature
Motor is overloaded
Protection is too finely
tuned for the duty cycle.
Rated Motor Efficiency
P0309 is not accurate.
Make sure that the load duty
cycle (temporary overload) lies
within the limits specified.
Verify P0640 is set for the
application.
Verify motor efficiency setup via
P0309 equals motor nameplate
data.
NOTE: Set P0003=3 and P0010=1
and then advance to P0309. Set
efficiency to motor rated efficiency,
or 99. Advance to P3900=3.
Off2
F0012,
SED2
temperature
signal lost
Wire breakage of the SED2
temperature sensor (heat
sink).
— Off2
F0015, Moto
r
temperature
signal lost
Breakage or short-circuit
of the motor temperature
sensor.
If a signal loss is
detected, temperature
monitoring switches to
monitoring the thermic
motor image.
— Off2
F0020, 1
phase for
input power
supply
missing
One of the 3 phases of the
input power supply voltage
is missing.
Check wiring of the 3 phases at the
SED2 input supply voltage.
Off2