Technical data

SED2 Operation and Maintenance Manual
92 Siemens Building Technologies, Inc
Parameter
Description Unit
User
Setting
Min Default Max
Access
Level
P1820 Reverse output phase
sequence
- 0 0 1 2
Motor Data (P0004=3)
Parameter
Description Unit
User
Setting
Min Default Max
Access
Level
r0000 Drive display (defined in
P0005)
- - - - X
P0003 User access level to
parameters
- 0 1 4 1
P0004 Parameter filter - 0 0 22 1
P0010 Commissioning parameter
filter
- 0 0 30 1
r0035 CO: Act. Motor temperature °C - - - 2
P0304 Rated motor voltage V 10 230 2000 1
P0305 Rated motor current A 0.01 3.25 10000.00 1
P0307 Rated motor power - 0.01 0.75 2000.00 1
P0308 Rated motor cosPhi - 0.000 0.000 1.000 2
P0309 Rated motor efficiency % 0.0 0.0 99.9 2
P0310 Rated motor frequency Hz 12.00 50.00 or 60.00
650.00 1
P0311 Rated motor speed 1/min 0 0 40000 1
r0313 Motor pole pairs - - - - 3
P0340 Calculation of motor
parameters
- 0 0 4 2
P0350 Stator resistance (line-to-line) ohm 0.00001 4.0 2000.0 2
r0395 CO: Total stator resistance
[%]
% - - - 3
P0601 Motor temp. sensor - 0 0 2 3
P0610 Motor I2t temperature reaction
- 0 2 2 3
P0640 Motor overload factor [%] % 10.0 150.0 400.0 2
P1910 Select motor data
identification
ohm 0 0 20 2
r1912 Identified stator resistance - - - - 2
Commands and Digital I/O (P0004=7)
Parameter
Description Unit
User
Setting
Min Default Max
Access
Level
r0000 Drive display (defined in
P0005)
- - - - X
r0002 Drive state (actual) - - - - 2
P0003 User access level to
parameters
- 0 1 4 1
P0004 Parameter filter - 0 0 22 1
P0010 Commissioning parameter
filter
- 0 0 30 1
r0019 CO/BO: BOP control word - - - - 3
r0050 CO: Active command data set
- - - - 2
r0052 CO/BO: Act. status word 1 - - - - 2
r0053 CO/BO: Act. status word 2 - - - - 2
r0054 CO/BO: Act. control word 1 - - - - 3
r0055 CO/BO: Add. act. control word
- - - - 3
P0700 Selection of command source - 0 2 6 1
P0701 Function of digital input 1 - 0 1 99 2
P0702 Function of digital input 2 - 0 12 99 2
P0703 Function of digital input 3 - 0 9 99 2
P0704 Function of digital input 4 - 0 15 99 2
P0705 Function of digital input 5 - 0 15 99 2