Technical data
SED2 Operation and Maintenance Manual
94 Siemens Building Technologies, Inc
Parameter
Description Unit
User
Setting
Min Default Max
Access
Level
P0771 CI: DAC - 0:0 21:0 4000:0 2
P0773 Smooth time DAC ms 0 2 1000 3
r0774 Act. DAC value [V] or [mA] - - - - 2
P0776 Type of DAC - 0 1 1 3
P0777 Value x1 of DAC scaling % -99999.0 0.0 99999.0 2
P0778 Value y1 of DAC scaling - 0 0 20 2
P0779 Value x2 of DAC scaling % -99999.0 100.0 99999.0 2
P0780 Value y2 of DAC scaling - 0 20 20 2
P0781 Width of DAC deadband - 0 0 20 2
Setpoint Channel and Ramp Generator (P0004=10)
Parameter
Description Unit
User
Setting
Min Default Max
Access
Level
r0000 Drive display (defined in
P0005)
- - - - X
P0003 User access level to
parameters
- 0 1 4 1
P0004 Parameter filter - 0 0 22 1
P0010 Commissioning parameter
filter
- 0 0 30 1
P1000 Selection of frequency
setpoint
- 0 2 77 1
P1001 Fixed frequency 1 Hz -650.0 0.00 650.00 2
P1002 Fixed frequency 2 Hz -650.0 0.00 650.00 2
P1003 Fixed frequency 3 Hz -650.0 0.00 650.00 2
P1004 Fixed frequency 4 Hz -650.0 0.00 650.00 2
P1005 Fixed frequency 5 Hz -650.0 0.00 650.00 2
P1006 Fixed frequency 6 Hz -650.0 0.00 650.00 2
P1007 Fixed frequency 7 Hz -650.0 0.00 650.00 2
P1008 Fixed frequency 8 Hz -650.0 0.00 650.00 2
P1009 Fixed frequency 9 Hz -650.0 0.00 650.00 2
P1010 Fixed frequency 10 Hz -650.0 0.00 650.00 2
P1011 Fixed frequency 11 Hz -650.0 0.00 650.00 2
P1012 Fixed frequency 12 Hz -650.0 0.00 650.00 2
P1013 Fixed frequency 13 Hz -650.0 0.00 650.00 2
P1014 Fixed frequency 14 Hz -650.0 0.00 650.00 2
P1015 Fixed frequency 15 Hz -650.0 0.00 650.00 2
P1016 Fixed frequency mode-Bit 0 - 1 1 3 3
P1017 Fixed frequency mode-Bit 1 - 1 1 3 3
P1018 Fixed frequency mode-Bit 2 - 1 1 3 3
P1019 Fixed frequency mode-Bit 3 - 1 1 3 3
r1024 CO: Act. fixed frequency Hz - - - 3
P1025 Fixed frequency mode – Bit 4 - 1 1 3 3
P1027 Fixed frequency mode – Bit 5 - 1 1 3 3
P1031 Setpoint memory of the MOP - 0 0 1 2
P1032 Inhibit reverse direction of
MOP
- 0 1 1 2
P1040 Setpoint of the MOP Hz -650.00 5.00 650.00 2
r1050 CO: Act. Output freq. of the
MOP
- - - - 3
r1078 CO: Total frequency setpoint Hz - - - 3
P1080 Min. Frequency Hz 0.00 0.00 650.00 1
P1082 Max. Frequency Hz 0.00 50.00 650.00 1
P1091 Skip frequency 1 Hz 0.00 0.00 650.00 3
P1092 Skip frequency 2 Hz 0.00 0.00 650.00 3
P1093 Skip frequency 3 Hz 0.00 0.00 650.00 3
P1094 Skip frequency 4 Hz 0.00 0.00 650.00 3
P1101 Skip frequency bandwidth Hz 0.00 2.00 10.00 3