Technical data

Appendix A: Parameter Reference List
Siemens Building Technologies, Inc. 99
Parameter List
r0000 Drive display (defined in P0005)
Min: - Def: - Max: -
Level X
Note:
Pressing the "Fn" button for 2 seconds allows you to view the values of DC link voltage, output current, output frequency,
and chosen r0000 setting (defined in P0005).
r0002 Drive state (actual)
Min: - Def: - Max: -
Level 2
Enum:
0=Commissioning mode (P0010=0)
1=Drive ready
2=Drive fault active
3=Drive starting (DC-link precharging)
4=Drive running
5=Stopping (ramping down)
Dependency:
State 3 visible only while precharging DC link, and when externally powered communications board is fitted.
P0003 User access level to parameters
Min: 0 Def: 1 Max: 4
Level 1
Enum:
0=User-defined parameter list-see P0013 for details
1=Standard: Access into frequently used parameters.
2=Extended: Access to for example, inverter I/O
functions.
3=Expert: For expert use only.
4=Service: Only for use by authorized service personal-
password protected.
P0004 Parameter filter
Min: 0 Def: 0 Max: 22
Level 1
Example:
P0004=22 specifies that only PID parameters will be visible.
Enum:
0=All parameters
2=Inverter
3=Motor
4=Speed sensor
5=Technol. application/units
7=Commands, binary I/O
8=ADC and DAC
10 =Setpoint channel/RFG
12 =Drive features
13 =Motor control
20 =Communication
21 =Alarms/warnings/monitoring
22 =Technology controller (for
example, PID)
Dependency:
Parameters marked "Quick Comm: Yes" in the parameter header can only be set when P0010=1 (Quick Commissioning).
Note:
The inverter will start with any setting of P0004.
P0005 Display selection for r0000
Min: 2 Def: 21 Max: 2294
Level 2
Enum:
21=Actual frequency 25=Output voltage 26=DC link voltage 27=Output current
Note:
These settings refer to read only parameter numbers ("rxxxx").
Details:
See relevant "rxxxx" parameter descriptions.
P0006 Display mode for r0000
Min: 0 Def: 2 Max: 4
Level 3
Enum:
0=In Ready state alternate between setpoint and output freq.
In run display output freq.
1=In Ready state display setpoint. In run display output freq.
2=In Ready state alternate between P0005 value and r0020
value. In run display P0005 value.
3=In Ready state alternate between r0002 value and
r0020 value. In run display r0002 value
4=In all states just display P0005
Note:
When inverter is not running, the display alternates between the values for "Not Running" and "Running".
Per default, the setpoint and actual frequency values are displayed alternately.
P0010 Commissioning parameter filter
Min: 0 Def: 0 Max: 30
Level 1
Enum:
0=Ready
1=Quick commissioning
2=Inverter
29 =Download
30 =Factory setting
Dependency:
Reset to 0 for interter to run.
P0003 (user access level) also determines access to parameters.
Note:
If P3900 is not 0 (0 is the default value), this parameter is automatically reset to 0.
P0011 Lock for user-defined parameter
Min: 0 Def: 0 Max: 65535
Level 3
Details:
See P0013 (user-defined parameter).
P0012 Key for user-defined parameter
Min: 0 Def: 0 Max: 65535
Level 3
Details:
See P0013 (user-defined parameter).
P0013[20] User-defined parameter
Min: 0 Def: 0 Max: 65535
Level 3