Technical data
SED2 Operation and Maintenance Manual
100 Siemens Building Technologies, Inc
Instructions:
1. Step 1: Set P0003=3 (expert user)
2. Step 2: Go to P0013 indices 0 to 16 (user list)
3. Step 3: Enter into P0013 index 0 to 16 the parameters required to be visible in the user-defined list. The following
values are fixed and cannot be changed:
- P0013 index 19=12 (key for user-defined parameter)
- P0013 index 18=10 (commissioning parameter filter)
- P0013 index 17= 3 (user access level)
4. Step 4: Set P0003=0 to activate the user-defined parameter.
Dependency:
First, set P0011 ("lock") to a different value than P0012 ("key") to prevent changes to user-defined parameter. Then, set
P0003 to 0 to activate the user-defined list.
When locked and the user-defined parameter is activated, the only way to exit the user-defined parameter (and view other
parameters) is to set P0012 ("key") to the value in P0011 ("lock").
Note:
Alternatively, set P0010=30 (commissioning parameter filter=factory setting) and P0970=1 (factory reset) to perform a
complete factory reset.
The default values of P0011 ("lock") and P0012 ("key") are the same.
r0018 Firmware version
Min: - Def: - Max: -
Level 1
r0019 CO/BO: BOP control word
Min: - Def: - Max: -
Level 3
Bit Fields:
Bit00 ON/OFF1 0 NO, 1 YES
Bit01 OFF2: Electrical stop 0 YES, 1 NO
Bit02 OFF3: Fast stop 0 YES, 1 NO
Bit08 JOG right 0 NO, 1 YES
Bit09 JOG left 0 NO, 1 YES
Bit11 Reverse (setpoint inversion) 0 NO, 1 YES
Bit13 Motor potentiometer MOP up 0 NO, 1 YES
Bit14 Motor potentiometer MOP down 0 NO, 1 YES
Note:
When BICO technology is used to allocate functions to panel buttons, this parameter displays the actual status of the
relevant command.
The following functions can be "connected" to individual buttons:
- ON/OFF1 - JOG - INCREASE
- OFF2 - REVERSE - DECREASE
r0020 CO: Act. frequency setpoint
Min: - Def: - Max: -
Level 3
r0021 CO: Act. frequency
Min: - Def: - Max: -
Level 2
r0022 Act. rotor speed
Min: - Def: - Max: -
Level 3
Note:
This calculation makes no allowance for load-dependent slip.
r0024 CO: Act. output frequency
Min: - Def: - Max: -
Level 3
r0025 CO: Act. output voltage
Min: - Def: - Max: -
Level 2
r0026[2] CO: Act. OuDC linktput voltage
Min: - Def: - Max: -
Level 2
r0027 CO: Act. output current
Min: - Def: - Max: -
Level 2
r0031 CO: Act. Torque
Min: - Def: - Max: -
Level 3
r0032 CO: Act. Power
Min: - Def: - Max: -
Level 3
Dependency:
Value is displayed in [kW] or [hp] depending on setting for P0100 (operation for Europe/North America).
r0035 CO: Act. Motor temperature
Min: - Def: - Max: -
Level 2
r0039 CO: Energy consumpt. meter [kWh]
Min: - Def: - Max: -
Level 2
Dependency:
Value is reset when P3900=1 (end quick commissioning), P0970=1 (factory reset) or P0040=1 (reset energy consumption
meter).