Technical data

Appendix A: Parameter Reference List
Siemens Building Technologies, Inc. 101
P0040 Reset energy consumption meter
Min: 0 Def: 0 Max: 1
Level 2
Enum:
0=No reset, 1=Reset r0039 to 0.
Dependency:
No reset until "P" is pressed.
r0050 CO: Active command data set
Min: - Def: - Max: -
Level 2
Enum:
0=1st. Command data set (CDS) 1=2nd. Command data set (CDS) 2=3rd. Command data set (CDS)
r0052 CO/BO: Act. status word 1
Min: - Def: - Max: -
Level 2
Bit Fields:
Bit00 Drive ready 0 NO, 1 YES
Bit01 Drive ready to run 0 NO, 1 YES
Bit02 Drive running 0 NO, 1 YES
Bit03 Drive fault active 0 NO, 1 YES
Bit04 OFF2 active 0 YES, 1 NO
Bit05 OFF3 active 0 YES, 1 NO
Bit06 ON inhibit active 0 NO, 1 YES
Bit07 Drive warning active 0 NO, 1 YES
Bit08 Deviation setp/act value 0 YES, 1 NO
Bit09 PZD control 0 NO, 1 YES
Bit10 Maximum frequency reached 0 NO, 1 YES
Bit11 Warning: Motor current limit 0 YES, 1 NO
Bit12 Motor holding brake active 0 NO, 1 YES
Bit13 Motor overload 0 YES, 1 NO
Bit14 Motor runs direction right 0 NO, 1 YES
Bit15 Inverter overload 0 YES, 1 NO
Note:
Output of Bit3 (Fault) will be inverted on digital output=No Fault.
r0053 CO/BO: Act. status word 2
Min: - Def: - Max: -
Level 2
Bit Fields:
Bit00 DC brake active 0 NO, 1 YES
Bit01 Act. freq. r0024 > P2167 0 NO, 1 YES
Bit02 Act. freq. r0024 > P1080 0 NO, 1 YES
Bit03 Act. current r0027 >= P2170 0 NO, 1 YES
Bit04 Act. freq. r0024 > P2155 0 NO, 1 YES
Bit05 Act. freq. r0024 <= P2155 0 NO, 1 YES
Bit06 Act. freq. r0024 >= setpoint 0 NO, 1 YES
Bit07 Act. Vdc r0026 < P2172 0 NO, 1 YES
Bit08 Act. Vdc r0026 > P2172 0 NO, 1 YES
Bit09 Ramping finished 0 NO, 1 YES
Bit10 PID output r2294 < P2291 0 NO, 1 YES
Bit11 PID output r2294 >= P2291 0 NO, 1 YES
Bit14 Download data set 0 from AOP 0 NO, 1 YES
Bit15 Download data set 1 from AOP 0 NO, 1 YES
Details:
See description of seven segment display.