Technical data

SED2 Operation and Maintenance Manual
102 Siemens Building Technologies, Inc
r0054 CO/BO: Act. control word 1
Min: - Def: - Max: -
Level 3
Bit Fields:
Bit00 ON/OFF1 0 NO, 1 YES
Bit01 OFF2: Electrical stop 0 YES, 1 NO
Bit02 OFF3: Fast stop 0 YES, 1 NO
Bit03 Pulse enable 0 NO, 1 YES
Bit04 RFG enable 0 NO, 1 YES
Bit05 RFG start 0 NO, 1 YES
Bit06 Setpoint enable 0 NO, 1 YES
Bit07 Fault acknowledge 0 NO, 1 YES
Bit08 JOG right 0 NO, 1 YES
Bit09 JOG left 0 NO, 1 YES
Bit10 Control from PLC 0 NO, 1 YES
Bit11 Reverse (setpoint inversion) 0 NO, 1 YES
Bit13 Motor potentiometer MOP up 0 NO, 1 YES
Bit14 Motor potentiometer MOP down 0 NO, 1 YES
Bit15 CDS Bit 0 (Local/Remote) 0 NO, 1 YES
Details:
See description of seven segment display.
r0055 CO/BO: Add. act. control word
Min: - Def: - Max: -
Level 3
Bit Fields:
Bit00 Fixed frequency Bit 0 0 NO, 1 YES
Bit01 Fixed frequency Bit 1 0 NO, 1 YES
Bit02 Fixed frequency Bit 2 0 NO, 1 YES
Bit03 Fixed frequency Bit 3 0 NO, 1 YES
Bit08 PID enabled 0 NO, 1 YES
Bit09 DC brake enabled 0 NO, 1 YES
Bit11 Droop 0 NO, 1 YES
Bit12 Torque control 0 NO, 1 YES
Bit13 External fault 1 0 YES, 0 NO
Details:
See description of seven segment display.
r0056 CO/BO: Status of motor control
Min: - Def: - Max: -
Level 3
Bit Fields:
Bit00 Init. control finished 0 NO, 1 YES
Bit01 Motor demagnetizing finished 0 NO, 1 YES
Bit02 Pulses enabled 0 NO, 1 YES
Bit03 Voltage soft start select 0 NO, 1 YES
Bit04 Motor excitation finished 0 NO, 1 YES
Bit05 Starting boost active 0 NO, 1 YES
Bit06 Acceleration boost active 0 NO, 1 YES
Bit07 Frequency is negative 0 NO, 1 YES
Bit08 Field weakening active 0 NO, 1 YES
Bit09 Volts setpoint limited 0 NO, 1 YES
Bit10 Slip frequency limited 0 NO, 1 YES
Bit11 F_out > F_max Freq. limited 0 NO, 1 YES
Bit12 Phase reversal selected 0 NO, 1 YES
Bit13 I-max controller active 0 NO, 1 YES
Bit14 Vdc-max controller active 0 NO, 1 YES
Bit15 Vdc-min controller active 0 NO, 1 YES
Details:
See description of seven segment display.
r0061 CO: Act. rotor speed
Min: - Def: - Max: -
Level 3
r0086 CO: Act. active current
Min: - Def: - Max: -
Level 3
Dependency:
Applies when V/f control is selected in P1300 (control mode); otherwise, the display shows the value zero.