Technical data

Appendix A: Parameter Reference List
Siemens Building Technologies, Inc. 103
P0100 Europe/North America power settings [kW or hp]
Min: 0 Def: 0 Max: 2
Level 1
Enum:
0=Europe [kW], frequency default 50 Hz
1=North America [hp], frequency default 60 Hz
2=North America [kW], frequency default 60 Hz
The setting of DIP switch 2 under the I/O board determines the validity of settings 0 and 1 for P0100 according to the
following table:
DIP 2 Setting Meaning P0100 Setting Meaning
Off [kW], frequency default 50 [Hz] Overwrites 1 [hp], frequency default 60
[Hz]
On [hp], frequency default 60 [Hz] Overwrites 0 [kW], frequency default 50
[Hz]
Dependency:
Stop drive first (that is, disable all pulses) before you change this parameter.
P0010=1 (commissioning mode) enables changes to be made.
Changing P0100 resets all rated motor parameters as well as other parameters that depend on the rated motor parameters
(see P0340-calculation of motor parameters).
Note:
P0100 setting 2 (==> [kW], frequency default 60 [Hz]) is not overwritten by the setting of DIP switch 2 (see table above).
r0200 Act. power stack code number (per following table)
Min: - Def: - Max: -
Level 3
Note:
Parameter r0200=0 indicates that no power stack has been identified.
r0206 Rated inverter power [kW]/[hp]
Min: - Def: - Max: -
Level 2
Dependency:
Value is displayed in [kW] or [hp] depending on setting for P0100 (operation for Europe/North America).
r0207 Rated inverter current
Min: - Def: - Max: -
Level 2
r0208 Rated inverter voltage
Min: - Def: - Max: -
Level 2
Value:
r0208=230 : 200-240V +/- 10% r0208=400 : 380-480V +/- 10% r0208=575 : 500-600V +/- 10%
r0209 Maximum inverter current
Min: - Def: - Max: -
Level 2
P0304 Rated motor voltage
Min: 10 Def: 230 Max: 2000
Level 1
Dependency:
Changeable only when P0010=1 (quick commissioning).
P0305 Rated motor current
Min: 0.01 Def: 3.25 Max: 10000.00
Level 1
Dependency:
Changeable only when P0010=1 (quick commissioning).
Depends also on P0320 (motor magnetization current).
Note:
For asynchronous motors, the maximum value is defined as the maximum inverter current (r0209).
For synchronous motors, the maximum value is defined as twice the maximum inverter current (r0209)
The minimum value is defined as 1/32 times inverter rated current (r0207).
P0307 Rated motor power
Min: 0.01 Def: 0.75 Max: 2000.00
Level 1
Dependency:
If P0100=1 ([kW],frequency default 50 Hz), values will be in [hp]-see diagram P0304 (rating plate).
Changeable only when P0010=1 (quick commissioning).
P0308 Rated motor cosPhi
Min: 0.000 Def: 0.000 Max: 1.000
Level 2
Dependency:
Changeable only when P0010=1 (quick commissioning).
Visible only when P0100=0 or 2, (motor power entered in [kW]).
Setting 0 causes internal calculation of value (see r0332).
P0309 Rated motor efficiency
Min: 0.0 Def: 0.0 Max: 99.9
Level 2
Dependency:
Changeable only when P0010=1 (quick commissioning).
Visible only when P0100=1, (that is, motor power entered in [hp]).
Setting 0 causes internal calculation of value (see r0332).
Note:
P0309=100% corresponds to superconducting