Technical data
Appendix A: Parameter Reference List
Siemens Building Technologies, Inc. 105
P0506[10] Parameter List
Min: 0 Def: 754 Max: 4000
Level 3
Index:
P0506[0] : Parameter 1
P0506[1] : Parameter 2
P0506[2] : Parameter 3
P0506[3] : Parameter 4
P0506[4] : Parameter 5
P0506[5] : Parameter 6
P0506[6] : Parameter 7
P0506[7] : Parameter 8
P0506[8] : Parameter 9
P0506[9] : Parameter 10
P0507[3] Scalar values
Min: 0 Def: 1.0 Max: 9999.9
Level 3
Index:
P0507[0] :Scalar numerator P0507[1] : Scalar denominator P0507[2] : Scalar offset
P0508[4] Unit
Min: 0 Def: 0 Max: 65535
Level 3
Index:
P0508[0] :Unit character 1 P0508[1] : Unit character 2 P0508[2] : Unit character 3 P0508[3] : Unit character 4
P0509[12] String
Min: 0 Def: 0 Max: 65535
Level 3
Index:
P0509[0] : String char 1
P0509[1] : String char 2
P0509[2] : String char 3
P0509[3] : String char 4
P0509[4] : String char 5
P0509[5] : String char 6
P0509[6] : String char 7
P0509[7] : String char 8
P0509[8] : String char 9
P0509[9] : String char 10
P0509[10] : String char 11
P0509[11] : String char 12
P0601 Motor temperature sensor
Min: 0 Def: 0 Max: 2
Level 3
Setting:
0=No sensor 1=PTC thermistor 2=KTY84
Dependency:
If no sensor is selected, motor temperature monitoring occurs based on the estimated value of the thermal motor model.
P0610 Motor I2t temperature reaction
Min: 0 Def: 2 Max: 2
Level 3
Enum:
0=No reaction, warning only 1=Warning and Imax reduction (results in reduced output freq.)
2=Warning and trip (F0010)
P0640 Motor overload factor [%]
Min: 10.0 Def: 150.0 Max: 400.0
Level 2
Dependency:
Limited to maximum inverter current or to 400% of rated motor current (P0305), whichever is the lower
P0700[2] Selection of command source
Min: 0 Def: index dependent Max: 6
Level 1
Enum:
0=Factory default setting
1=BOP (keypad)
2=Terminal
4=USS on BOP link
5=USS on COM link
6=CB on COM link
Index:
P0700[0] : IN000 (AUTO) 1st. Command data set (CDS) P0700[1] : IN001 (HAND) 2nd. Command data set (CDS)
Note:
Changing this parameter resets (to default) all settings on item selected. For example: changing from 1 to 2 resets all digital
inputs to default settings.
P0701[2] Function of digital input 1
Min: 0 Def: 1 Max: 99
Level 2
Enum:
0=Digital input disabled
1=ON/OFF1
2=ON reverse /OFF1
3=OFF2 -coast to standstill
4=OFF3 -quick ramp-down
9=Fault acknowledge
10 =JOG right
11 =JOG left
12 =Reverse
13 =MOP up (increase freq.)
14 =MOP down (decrease freq.)
15 =Fixed setpoint (Direct selection)
16 =Fixed setpoint (Direct selection + ON)
17 =Fixed setpoint (Binary coded selection+ON)
25 =DC brake enable
26 =Enable Essential Service
27 =Enable PID
29 =External trip
33 =Disable additional freq setpoint
99 =Enable BICO parameterization
Index:
P0701[0] : IN000 (AUTO) 1st. Command data set (CDS) P0701[1] : IN001 (HAND) 2nd. Command data set (CDS)
Dependency:
Setting 99 (enable BICO parameterization) requires P0700 (command source) or P3900 (end of quick commissioning)=1, 2
or P0970 (factory reset)=1 in order to reset.
Note:
Setting 99 (BICO) for expert use only
P0702[2] Function of digital input 2
Min: 0 Def: 12 Max: 99
Level 2
Detail:
See P0701 (function of digital input1).
P0703[2] Function of digital input 3
Min: 0 Def: 9 Max: 99
Level 2
Detail:
See P0701 (function of digital input1).
P0704[2] Function of digital input 4
Min: 0 Def: 15 Max: 99
Level 2
Detail:
See P0701 (function of digital input1).