Technical data

SED2 Operation and Maintenance Manual
106 Siemens Building Technologies, Inc
P0705[2] Function of digital input 5
Min: 0 Def: 15 Max: 99
Level 2
Detail:
See P0701 (function of digital input1).
P0706[2]
Function of digital input 6
Min: 0 Def: 15 Max: 99
Level 2
Detail:
See P0701 (function of digital input1).
P0707[2] Function of digital input 7
Min: 0 Def: 0 Max: 99
Level 2
Enum:
0=Digital input disabled
1=ON/OFF1
2=ON reverse /OFF1
3=OFF2 -coast to standstill
4=OFF3 -quick ramp-down
9=Fault acknowledge
10 =JOG right
11 =JOG left
12 =Reverse
13 =MOP up (increase freq.)
14 =MOP down (decrease freq.)
25 =DC brake enable
26 =Enable Essential Service
29 =External trip
33 =Disable additional freq setpoint
99 =Enable BICO parameterization
Index:
P0707[0] : IN000 (AUTO) 1st. Command data set (CDS) P0707[1] : IN001 (HAND) 2nd. Command data set (CDS)
Dependency:
Signals about 4V are active, signals below 1.6V are inactive.
Details:
See P0701 (function of digital input 1).
P0708[2] Function of digital input 8
Min: 0 Def: 0 Max: 99
Level 2
Detail:
See P0707 (function of digital input7).
P0718 CO/BO: Hand/Auto
Min: 0 Def: 0 Max: 1
Level 2
r0722 CO/BO: Binary input values
Min: - Def: - Max: -
Level 2
Bit Fields
Bit00 Digital input 1 0 OFF, 1 ON
Bit01 Digital input 2 0 OFF, 1 ON
Bit02 Digital input 3 0 OFF, 1 ON
Bit03 Digital input 4 0 OFF, 1 ON
Bit04 Digital input 5 0 OFF, 1 ON
Bit05 Digital input 6 0 OFF, 1 ON
Bit06 Digital input 7 (via ADC 1) 0 OFF, 1 ON
Bit07 Digital input 8 (via ADC 2) 0 OFF, 1 ON
Note:
Segment is lit when signal is active.
P0725 PNP/NPN digital inputs
Min: 0 Def: 1 Max: 1
Level 3
Value:
NPN: Terminals 5/6/7 must be connected via terminal 9 (0V).
PNP: Terminals 5/6/7 must be connected via terminal 8 (24V).
If VCB NPN: Terminals 5/6/7/8/16/17 must be connected via terminal 28 (0V).
PNP: Terminals 5/6/7/8/16/17 must be connected via terminal 9 (24V).
Enum:
0=NPN mode ==> low active 1=PNP mode ==> high active
P0731[2] BI: Function of digital output 1
Min: 0.0 Def: 52.3 Max: 4000.0
Level 2
Settings:
52.0 Drive ready 0 Closed
52.1 Drive ready to run 0 Closed
52.2 Drive running 0 Closed
52.3 Drive fault active 0 Closed
52.4 OFF2 active 1 Closed
52.5 OFF3 active 1 Closed
52.6 Switch on inhibit active 0 Closed
52.7 Drive running 0 Closed
52.8 Deviation setpoint/actual value 1 Closed
52.9 PZD control (Process Data Control) 0 Closed
52.A Maximum frequency reached 0 Closed
52.B Warning: Motor current limit 1 Closed
52.C Motor holding brake (MHB) active 0 Closed
52.D Motor overload 1 Closed
52.E Motor running direction right 0 Closed
52.F Inverter overload 1 Closed
53.0 DC brake active 0 Closed
53.1 Inverter freq. less switch off limit 0 Closed
53.2 Inverter freq. less minimum freq. 0 Closed
53.3 Current greater or equal than limit 0 Closed
53.4 Act. freq. greater comparison freq. 0 Closed
53.5 Act. freq. less comparison freq. 0 Closed
53.6 Act. freq. greater/equal setpoint 0 Closed
53.7 Voltage less than threshold 0 Closed
53.8 Voltage greater than threshold 0 Closed
53.A PID output at lower limit (P2292) 0 Closed
53.B PID output at upper limit (P2291) 0 Closed
Index:
P0731[0] : IN000 (AUTO) 1st. Command data set (CDS) P0731[1] : IN001 (HAND) 2nd. Command data set (CDS)
P0732[2] BI: Function of digital output 2
Min: 0.0 Def: 52.7 Max: 4000.0
Level 2
Detail:
See P0731 (function of digital output 1).