r0948[12] Fault time
Min: - Def: - Max: -
Level 3
Data:
Time stamp to indicate when the fault has occurred. P2114 (run-time counter) or P2115 (real time clock) are the possible
sources of the time stamp.
Example:
The time is taken from P2115 if this parameter has been updated with the real time. If not, P2114 is used
Index:
r0948[0] : Recent fault trip --, fault time seconds+minutes
r0948[1] : Recent fault trip --, fault time hours+days
r0948[2] : Recent fault trip --, fault time month+year
r0948[3] : Recent fault trip -1, fault time seconds+minutes
r0948[4] : Recent fault trip -1, fault time hours+days
r0948[5] : Recent fault trip -1, fault time month+year
r0948[6] : Recent fault trip -2, fault time seconds+minutes
r0948[7] : Recent fault trip -2, fault time hours+days
r0948[8] : Recent fault trip -2, fault time month+year
r0948[9] : Recent fault trip -3, fault time seconds+minutes
r0948[10] : Recent fault trip -3, fault time hours+days
r0948[11] : Recent fault trip -3, fault time month+year‘
Note:
P2115 can be updated via AOP, Starter, DriveMonitor, etc.
r0949[8] Fault value
Min: - Def: - Max: -
Level 3
Index:
r0949[0] : Recent fault trip --, fault value 1
r0949[1] : Recent fault trip --, fault value 2
r0949[2] : Recent fault trip -1, fault value 3
r0949[3] : Recent fault trip -1, fault value 4
r0949[4] : Recent fault trip -2, fault value 5
r0949[5] : Recent fault trip -2, fault value 6
r0949[6] : Recent fault trip -3, fault value 7
r0949[7] : Recent fault trip -3, fault value 8
P0952 Total number of faults
Min: 0 Def: 0 Max: 0
Level 3
Dependency:
Setting 0 resets fault history (changing to 0 also resets parameter P0948-fault time).
r0967 Control word 1
Min: - Def: - Max: -
Level 3
Bit Fields:
Bit00 ON/OFF1 0 NO, 1 YES
Bit01 OFF2: Electrical stop 0 YES, 1 NO
Bit02 OFF3: Fast stop 0 YES, 1 NO
Bit03 Pulse enable 0 NO, 1 YES
Bit04 RFG enable 0 NO, 1 YES
Bit05 RFG start 0 NO, 1 YES
Bit06 Setpoint enable 0 NO, 1 YES
Bit07 Fault acknowledge 0 NO, 1 YES
Bit08 JOG right 0 NO, 1 YES
Bit09 JOG left 0 NO, 1 YES
Bit10 Control from PLC 0 NO, 1 YES
Bit11 Reverse (setpoint inversion) 0 NO, 1 YES
Bit13 Motor potentiometer MOP up 0 NO, 1 YES
Bit14 Motor potentiometer MOP down 0 NO, 1 YES
Bit15 CDS Bit 0 (Local/Remote) 0 NO, 1 YES
r0968 Statue word 1
Min: - Def: - Max: -
Level 3
Bit Fields:
Bit00 Drive ready 0 NO, 1 YES
Bit01 Drive ready to run 0 NO, 1 YES
Bit02 Drive running 0 NO, 1 YES
Bit03 Drive fault active 0 NO, 1 YES
Bit04 OFF2 active 0 YES, 1 NO
Bit05 OFF3 active 0 YES, 1 NO
Bit06 ON inhibit active 0 NO, 1 YES
Bit07 Drive warning active 0 NO, 1 YES
Bit08 Deviation setp./act. value 0 YES, 1 NO
Bit09 PZD control 0 NO, 1 YES
Bit10 Maximum frequency reached 0 NO, 1 YES
Bit11 Warning: Motor current limit 0 YES, 1 NO
Bit12 Motor holding brake active 0 NO, 1 YES
Bit13 Motor overload 0 YES, 1 NO
Bit14 Motor runs direction right 0 NO, 1 YES
Bit15 Inverter overload 0 YES, 1 NO