Technical data
Appendix A: Parameter Reference List
Siemens Building Technologies, Inc. 111
P0970 Factory reset
Min: 0 Def: 0 Max: 1
Level 1
Enum:
0=Disabled 1=Parameter reset
Dependency:
First set P0010=30 (factory settings)
Stop drive (that is, disable all pulses) before you can reset parameters to default values.
Note:
The following parameters retain their values after a factory reset:
P0918 (CB address)
P2010 (USS baud rate)
P2011 (USS address)
P0971 Transfer data from RAM to EEPROM
Min: 0 Def: 0 Max: 1
Level 3
Enum:
0=Disabled 1=Start transfer
Note:
All values in RAM are transferred to EEPROM.
Parameter is automatically reset to 0 (default) after successful transfer.
P1000[2] Selection of frequency setpoint
Min: 0 Def: index dependent Max: 77
Level 1
Data:
Selects frequency setpoint source. In the table of possible settings below, the main setpoint is selected from the least
significant digit (that is, 0 to 6) and any additional setpoint from the most significant digit (that is, x0 through to x6).
Example:
Setting 12 selects main setpoint (2) derived from analog input with additional setpoint (1) taken from the motor
potentiometer.
Settings:
1 Motor potentiometer setpoint
(keypad)
2 Analog input
3 Fixed frequency setpoint
4 USS on BOP link/AOP
5 USS on COM link
6 Communication board (CB) on COM
link/P1-N2 communications
Enum:
0=No main setpoint
1=MOP setpoint
2=Analog setpoint
3=Fixed frequency
4=USS on BOP link
5=USS on COM link
6=CB on COM link
7=Analog setpoint 2
10=No main setpoint + MOP setpoint
11=MOP setpoint + MOP setpoint
12=Analog setpoint + MOP setpoint
13=Fixed frequency + MOP setpoint
14=USS on BOP link + MOP setpoint
15=USS on COM link + MOP setpoint
16=CB on COM link + MOP setpoint
17=Analog setpoint 2 + MOP setpoint
20=No main setpoint + Analog setpoint
21=MOP setpoint + Analog setpoint
22=Analog setpoint + Analog setpoint
23=Fixed frequency + Analog setpoint
24=USS on BOP link + Analog setpoint
25=USS on COM link + Analog setpoint
26=CB on COM link + Analog setpoint
27=Analog setpoint 2 + Analog setpoint
30=No main setpoint + Fixed frequency
31=MOP setpoint + Fixed frequency
32=Analog setpoint + Fixed frequency
33=Fixed frequency + Fixed frequency
34=USS on BOP link + Fixed frequency
35=USS on COM link + Fixed frequency
36=CB on COM link + Fixed frequency
37=Analog setpoint 2 + Fixed frequency
40=No main setpoint + USS on BOP link
41=MOP setpoint + USS on BOP link
42=Analog setpoint + USS on BOP link
43=Fixed frequency + USS on BOP link
44=USS on BOP link + USS on BOP link
45=USS on COM link + USS on BOP link
46=CB on COM link + USS on BOP link
47=Analog setpoint 2 + USS on BOP link
50=No main setpoint + USS on COM link
51=MOP setpoint + USS on COM link
52=Analog setpoint + USS on COM link
53=Fixed frequency + USS on COM link
54=USS on BOP link + USS on COM link
55=USS on COM link + USS on COM link
56=CB on COM link + USS on COM link
57=Analog setpoint 2 + USS on COM link
60=No main setpoint + CB on COM link
61=MOP setpoint + CB on COM link
62=Analog setpoint + CB on COM link
63=Fixed frequency + CB on COM link
64=USS on BOP link + CB on COM link
65=USS on COM link + CB on COM link
66=CB on COM link + CB on COM link
67=Analog setpoint 2 + CB on COM link
70=No main setpoint + Analog setpoint 2
71=MOP setpoint + Analog setpoint 2
72=Analog setpoint + Analog setpoint 2
73=Fixed frequency + Analog setpoint 2
74=USS on BOP link + Analog setpoint 2
75=USS on COM link + Analog setpoint 2
76=CB on COM link + Analog setpoint 2
77=Analog setpoint 2 + Analog setpoint 2
Index:
P1000[0] : IN000 (AUTO) 1st. Command data set (CDS)
P1000[1] : IN001 (HAND) 2nd. Command data set (CDS)
Note:
Single digits denote main setpoints that have no additional setpoint.