Technical data
SED2 Operation and Maintenance Manual
112 Siemens Building Technologies, Inc
P1001 Fixed frequency 1
Min: -650.0 Def: 0.00 Max: 650.00
Level 2
There are three types of fixed frequencies:
1. Direct selection (P0701-P0706=15)
In this mode of operation 1 digital input selects 1 fixed frequency. If several inputs are active together, the selected
frequencies are summed, for example, FF1 + FF2 + FF3 + FF4 + FF5 + FF6.
2. Direct selection + ON command (P0701-P0706=16)
The fixed frequency selection combines the fixed frequencies with an ON command. In this mode of operation 1 digital
input selects 1 fixed frequency. If several inputs are active together, the selected frequencies are summed, for
example, FF1 + FF2 + FF3 + FF4 + FF5 + FF6.
3. Binary coded selection + ON command (P0701-P0706=17)
Select up to 16 fixed frequencies using this method. Select the fixed frequencies according to the following table:
DIN4 DIN3 DIN2 DIN1
OFF Inactive Inactive Inactive Inactive
P1001 FF1 Inactive Inactive Inactive
Active
P1002 FF2 Inactive Inactive
Active
Inactive
P1003 FF3 Inactive Inactive
Active Active
P1004 FF4 Inactive
Active
Inactive Inactive
P1005 FF5 Inactive
Active
Inactive
Active
P1006 FF6 Inactive
Active Active
Inactive
P1007 FF7 Inactive
Active Active Active
P1008 FF8
Active
Inactive Inactive Inactive
P1009 FF9
Active
Inactive Inactive
Active
P1010 FF10
Active
Inactive
Active
Inactive
P1011 FF11
Active
Inactive
Active Active
P1012 FF12
Active Active
Inactive Inactive
P1013 FF13
Active Active
Inactive
Active
P1014 FF14
Active Active Active Active
Data:
P1015 FF15
Active Active Active Active
Dependency:
Select fixed frequency operation (using P1000).
Inverter requries ON command to start in the case of direct selection (P0701 – P0706=15).
Note:
Fixed frequencies can be selected using the digital inputs, and can also be combined with an ON command.
P1002-P1015 Fixed frequency 2 through 15
Min: -650.00 Def: See Note below Max: 650.00
Level 2
Details:
See P1001 (fixed frequency 1).
Default fixed frequency setpoint values are as follows:
Fixed Frequency Default Fixed Frequency Default Fixed Frequency Default
1 0.00 6 25.00 11 50.00
2 5.00 7 30.00 12 55.00
3 10.00 8 35.00 13 60.00
4 15.00 9 40.00 14 65.00
Note:
5 20.00 10 45.00 15 65.00
P1016 – P1019 Fixed frequency mode-Bit 0 through 3
Min: 1 Def: 1 Max: 3
Level 3
Details:
Parameter P1016 defines the mode of Bit 0, Parameter P1017 defines the mode of Bit 1, Parameter P1018 defines the
mode of Bit 2, and Parameter P1019 defines the mode of Bit 3.
Enum:
1=Direct selection 2=Direct selection + ON command 3=Binary coded selection + ON command
Note:
See table in P1001 (fixed frequency 1) for a description of how to use fixed frequencies.
P1020[2] –
P1023[2]
BI: Fixed freq. selection Bit 0
Min: 0:0 Def: 0:0 Max: 4000:0
Level 3
Settings:
P1020= 722.0 ==> Digital input 1
P1021= 722.1 ==> Digital input 2
P1022= 722.2 ==> Digital input 3
P1023= 722.3 ==> Digital input 4
P1026= 722.4 ==> Digital input 5
P1028= 722.5 ==> Digital input 6
Index:
P1020[0] : 1st. Command data set (CDS) for Bit 0
P1021[0] : 1st. Command data set (CDS) for Bit 1
P1022[0] : 1st. Command data set (CDS) for Bit 2
P1023[0] : 1st. Command data set (CDS) for Bit 3
P1020[1] : 2nd. Command data set (CDS) for Bit 0
P1021[1] : 2nd. Command data set (CDS) for Bit 1
P1022[1] : 2nd. Command data set (CDS) for Bit 2
P1023[1] : 2nd. Command data set (CDS) for Bit 3
Dependency:
Accessible only if P0701-P0706=99 (function of digital inputs=BICO)
r1024
CO: Act. fixed frequency
Min: - Def: - Max: -
Level 3