Technical data
Appendix A: Parameter Reference List
Siemens Building Technologies, Inc. 119
P2010[2] USS baudrate
Min: 4 Def: 6 Max: 12
Level 2
Enum:
4= 2400 baud
5= 4800 baud
6= 9600 baud
7= 19200 baud
8= 38400 baud
9= 57600 baud
10=76800 baud
11=93750 baud
12 =115200 baud
Index:
P2010[0] : Serial interface COM link P2010[1] : Serial interface BOP link
P2011[2] USS address
Min: 0 Def: 0 Max: 31
Level 2
Index:
P2011[0] : Serial interface COM link P2011[1] : Serial interface BOP link
Note:
You can connect up to a further 30 inverters via the serial link (that is, 31 inverters in total) and control them with the USS
serial bus protocol.
P2014[2] USS telegram off time
Min: 0 Def: 0 Max: 65535
Level 3
Index:
P2014[0] : Serial interface COM link P2014[1] : Serial interface BOP link
Note:
By default (time set to 0), no fault is generated (that is, watchdog disabled).
P2040 CB telegram off time
Min: 0 Def: 20 Max: 65535
Level 3
Dependency:
Setting 0=watchdog disabled
P2041[5] CB parameter
Min: 0 Def: 0 Max: 65535
Level 3
Index:
P2041[0] : CB parameter 0
P2041[1] : CB parameter 1
P2041[2] : CB parameter 2
P2041[3] : CB parameter 3
P2041[4] : CB parameter 4
Note:
See relevant communication board manual for protocol definition and appropriate settings
r2050[8] CB parameter
Min: 0 Def: 0 Max: 65535
Level 3
Index:
r2050[0] : Received word 0
r2050[1] : Received word 1
r2050[2] : Received word 2
r2050[3] : Received word 3
r2050[4] : Received word 4
r2050[5] : Received word 5
r2050[6] : Received word 6
r2050[7] : Received word 7
Note:
The control words can be viewed as bit parameters r2032 and r2033.
P2051[8] CI: PZD to CB
Min: 0:0 Def: 52:0 Max: 4000:0
Level 3
Settings:
Status word 1=52
CO/BO: Act. status word 1 (see r0052)
Actual value 1= 21 inverter output frequency (see r0021)
Other BICO settings are possible
Index:
P2051[0] : Transmitted word 0
P2051[1] : Transmitted word 1
P2051[2] : Transmitted word 2
P2051[3] : Transmitted word 3
P2051[4] : Transmitted word 4
P2051[5] : Transmitted word 5
P2051[6] : Transmitted word 6
P2051[7] : Transmitted word 7
r2053[5] CB identification
Min: - Def: - Max: -
Level 3
Enum:
0=No CB option board
1=PROFIBUS DP
2=DeviceNet
56 not defined
Index:
r2053[0] : CB type (PROFIBUS=1)
r2053[1] : Firmware version
r2053[2] : Firmware version detail
r2053[3] : Firmware date (year)
r2053[4] : Firmware date (day/month)
r2054[7] CB diagnosis
Min: - Def: - Max: -
Level 3
Index:
r2054[0] : CB diagnosis 0
r2054[1] : CB diagnosis 1
r2054[2] : CB diagnosis 2
r2054[3] : CB diagnosis 3
r2054[4] : CB diagnosis 4
r2054[5] : CB diagnosis 5
r2054[6] : CB diagnosis 6
Note:
See relevant communications board manual.
P2100[3] Alarm number selection
Min: 0 Def: 0 Max: 65535
Level 3
Example:
If you want F0005 to perform an OFF3 instead of an OFF2, set P2100[0]=5, then select the desired reaction in P2101[0] (in
this case, set P2101[0]=3).
Note:
All fault codes have a default reaction to OFF2. Some fault codes caused by hardware trips (for example, overcurrent)
cannot be changed from the default reactions.