Fixed PID setpoint 1 through 15
Min: -200.00 Def: See Note Below Max: 200.00
Level 2
Defines Fixed PID Setpoint 1. In addition, you can set any of the digital input parameters to Fixed PID Setpoint via the
digital inputs (P0701-P0706).
There are three selection modes for the PID fixed setpoint:
1. Direct selection (P0701=15 or P0702=15, etc.).
In this mode of operation, 1 digital input selects one PID fixed setpoint.
2. Direct selection with ON command (P0701=16 or P0702=16, etc.).
Description as for 1), except that this type of selection issues an ON command concurrent with any setpoint selection.
3. 3 Binary Coded Decimal selection (P0701-P0706=17).
Using this method to select the PID Fixed Setpoint allows you to choose up to 16 different PID setpoints. The
setpoints are selected according to the following table:
DIN4 DIN3 DIN2 DIN1
OFF Inactive Inactive Inactive Inactive
P1001 FF1 Inactive Inactive Inactive
Active
P1002 FF2 Inactive Inactive
Active
Inactive
P1003 FF3 Inactive Inactive
Active Active
P1004 FF4 Inactive
Active
Inactive Inactive
P1005 FF5 Inactive
Active
Inactive
Active
P1006 FF6 Inactive
Active Active
Inactive
P1007 FF7 Inactive
Active Active Active
P1008 FF8
Active
Inactive Inactive Inactive
P1009 FF9
Active
Inactive Inactive
Active
P1010 FF10
Active
Inactive
Active
Inactive
P1011 FF11
Active
Inactive
Active Active
P1012 FF12
Active Active
Inactive Inactive
P1013 FF13
Active Active
Inactive
Active
P1014 FF14
Active Active Active Active
Details:
P1015 FF15
Active Active Active Active
Dependency:
P2000=1 required in user access level 2 to enable setpoint source.
In mode 1 (above):
ON command required to start motor (enable pulses).
In mode 2 (above):
If inputs programmed to PID fixed setpoint and selected together, the selected setpoints are summed.
You may mix different types of frequencies; however, remember that they will be summed if selected together.
P2201=100% corresponds to 4000 hex.
Default fixed PID setpoint values are as follows:
Fixed PID Default Fixed PID Default Fixed PID Default
1 0.00 6 50.00 11 100.00
2 10.00 7 60.00 12 110.00
3 20.00 8 70.00 13 120.00
4 30.00 9 80.00 14 130.00
Note:
5 40.00 10 90.00 15 130.00
P2216, P2217,
P2218, P2219
Fixed PID setpoint mode-Bit 0, Bit 1, Bit 2, and Bit 3
Min: 1 Def: 1 Max: 3
Level 3
Enum:
1=Direct selection 2=Direct selection + ON command 3=Binary coded selection + ON command
P2220[2] BI: Fixed PID setp. select Bit 0
Min: 0:0 Def: 0:0 Max: 4000:0
Level 3
Settings:
722.0=Digital input 1 (requires P0701 set to 99, BICO)
722.1=Digital input 2 (requires P0702 set to 99, BICO)
722.2=Digital input 3 (requires P0703 set to 99, BICO)
722.3=Digital input 4 (requires P0704 set to 99, BICO)
722.4=Digital input 5 (requires P0705 set to 99, BICO)
722.5=Digital input 6 (requires P0706 set to 99, BICO)
722.6=Digital input 7 (via analog input 1, requires P0707 set to 99)
722.7=Digital input 8 (via analog input 2, requires P0708 set to 99)
Index:
P2220[0] : IN000 (AUTO) 1st. Command data set (CDS) P2220[1] : IN001 (HAND) 2nd. Command data set (CDS)