Technical data

Appendix A: Parameter Reference List
Siemens Building Technologies, Inc. 127
P2380[3] Motor hours run
Min: 0 Def: 0 Max: 100000
Level 2
Index:
P2380[0] : Motor 1 hrs run P2380[1] : Motor 2 hrs run P2380[2] : Motor 3 hrs run
Note:
To reset the running hours, set the value to zero, any other value is ignored.
P2390 Hibernation frequency
Min: 0 Def: 0 Max: 650.00
Level 3
Details:
Hibernation frequency setpoint (frequency the motor output will turn off).
P2391 Hibernation timer
Min: 0 Def: 0 Max: 650.00
Level 3
Details:
Hibernation restart frequency (frequency the motor output will turn on).
P2392 Restart frequency
Min: 0 Def: 0 Max: 650.00
Level 3
Details:
Hibernation restart frequency (frequency the motor output will turn on).
P3900 End of quick commissioning
Min: 0 Def: 0 Max: 3
Level 1
Details:
Performs calculations necessary for optimized motor operation.
After completion of calculation, P3900 and P0010 (parameter groups for commissioning) are automatically reset to their
original value 0.
Enum:
0=No quick commissioning
1=Start quick commissioning with factory reset
2=Start quick commissioning
3=Start quick commissioning only for motor data
Dependency:
Changeable only when P0010=1 (quick commissioning)
Note:
When setting 1 is selected, only the parameter settings carried out via the commissioning menu "Quick commissioning",
are retained; all other parameter changes, including the I/O settings, are lost. Motor calculations are also performed.
When setting 2 is selected, only those parameters, which depend on the parameters in the commissioning menu "Quick
commissioning" (P0010=1) are calculated. The I/O settings are also reset to default and the motor calculations performed.
When setting 3 is selected, only the motor and controller calculations are performed. Exiting quick commissioning with this
setting saves time (for example, if only motor rating plate data have been changed).
Calculates a variety of motor parameters, overwriting previous values. These include P0344 (Level 3, motor weight), P0350
(Level 3, demagnetization time), P2000 (reference frequency), P2002 (Level 3, reference current).