Operation with a Residual Current Device (RCD)
If a residual current device (also called a GLCI or RCCB) is connected, the SED2 operates with
no interruptions under the following conditions:
A RCD, Type B is used.
The RCD must have a threshold current of 300 mA.
The neutral conductor in the system must be grounded.
Each RCD supplies only one SED2 (an no other loads).
The output cables must not exceed the following:
328 ft (100 m) shielded
164 ft (50 m) unshielded
Do not connect machines with a 3-phase power source fitted with EMC filters to the mains via an
earth leakage current circuit breaker (ELCB) or ground fault circuit interrupter (GFCI). (See DIN
VDE 0160, Section 6.5.)