Technical data
Chapter 5 – Commissioning
Siemens Building Technologies, Inc. 23
DIP Switch Settings
Motor Frequency & Units of
Measurement Switches
In all versions of the SED2, the DIP switches for
selecting the motor frequency and North American
or European units of measurement are located on
the control board under the I/O module. (See
Chapter 4, Access to Connection Terminals for
I/O module and control board locations.) The I/O
module, located under the operator panel,
connects to the operator panel either directly
(frame sizes A through C/IP20) or via a cable
(frame sizes D through E and all IP54 models).
Analog Input Switches
For all versions of the SED2, the DIP switches
used to configure the analog inputs are located
on the I/O module. (See Chapter 4, Access to
Connection Terminals for I/O module locations.)
The I/O module, located under the operator
panel, connects to the operator panel either
directly (frame sizes A through C/IP20) or via a
cable (frame sizes D through E and all IP54
models).
DIP
Switch
Position Function DIP
Switch
Position Function
ON North American operation
(60 Hz, hp).
1 OFF Analog Input 1, voltage
0-10 Vdc, factory default.
2
OFF European operation (50 Hz, kW),
factory default.
1 ON Analog Input 1, current
0-20 mA.
2 OFF Analog Input 2, voltage
0-10 Vdc, factory default.
1 OFF Not for customer use.
NOTE: This switch must
be in the OFF
position for correct
SED2 operation.
2 ON Analog Input 2, current
0-20 mA.
20 21 22 23 24 25
29 3017 26 27 2812 13 14 15 16
10 11678912345
ON
12
ON
12
I/O module
SED2 frame size A
DIP switches for
analog inputs
DIP switches
for setting
mains frequency
5192Z13en
Figure 19. Location of DIP Switches.