Technical data

Chapter 5 – Commissioning
Siemens Building Technologies, Inc. 27
Default Commissioning Settings
Default settings for operation with the BOP are as follows:
Parameter Description Default Value for North America
(Europe)
P0100 For USA or Europe power
setting
0 = 50 Hz, kW (Europe), factory default
1 = 60 Hz, hp (North America)
2 = 60 Hz, kW (North America)
The setting of Motor Frequency & Units of Measurement DIP
switch 2 overwrites P0100 settings 0 and 1. See the DIP Switch
Settings section for details.
NOTES:
1. Stop the drive (that is, disable all pulses) before changing this
parameter.
2. Commissioning Parameter Filter P0010=1 (quick
commissioning mode) enables changes via P0100.
3. Changing P0100 resets all rated motor parameters as well as
other parameters that depend on the rated motor parameters
(see P0340, Calculation of Motor Parameters).
P0307 Nominal motor power Value in hp or kW depending on setting of P0100.
Default for P0307 is 0.75.
P0010=1 (commissioning mode) enables changes via P0307.
P0308 or
P0309
Rated motor cosPhi (P0308)
or
Rated motor efficiency
(P0309)
P0308 displays when P0100=0 or 2 and P0307 motor power is
entered in kW. Default for P0308 is 0.000.
P0309 displays when P0100=1 and P0307 motor power is entered
in hp. Default for P0309 is 0.0.
NOTE: P0309=100% corresponds to superconducting.
P0010=1 (commissioning mode) enables changes via P0308 or
P0309.
P0310 Nominal motor frequency 60 Hz or 50 Hz (default). Pole pair number is recalculated
automatically if the parameter is changed.
P0010=1 (commissioning mode) enables changes via P0310.
P0311 Nominal motor speed
1680 (1395) U/min (depends on model); default for P0311 is 0.
A setting of 0 causes an internal calculation of the value.
Vector control and V/f control with speed controller require this
value. Slip compensation in V/f control requires this value for
correct operation. Pole pair number is recalculated automatically if
the parameter is changed.
P0010=1 (commissioning mode) enables changes via P0311.
P0640 Motor overload factor, % Limited to a maximum inverter current or up to 400% of rated motor
current (P0305), whichever is lower.
Default for P0640 is 150.0.
Continued