Technical data
Chapter 5 – Commissioning
Siemens Building Technologies, Inc. 29
Motor Data for Commissioning Parameters
Motor parameters can only be modified if Commissioning Parameter Filter P0010=1 (for quick
commissioning). The motor control functions of the BOP are disabled by default. Set Selection of
Command Source parameter P0700[0]=1 (for BOP) and Selection of Frequency Setpoint P1000[0]=1
(for motor potentiometer setpoint) to enable motor control using the BOP.
If the BOP was configured for I/O control (P0700[0] is set to 1), the motor stops when the BOP is
removed.