Technical data
SED2 Operation & Maintenance Manual
30 Siemens Building Technologies, Inc.
Quick Commissioning Procedure
P0010 Start Quick Commissioning
0 = Ready to Run
1 = Quick Commissioning
30 = Factory Setting
NOTE: P0010 must always be set back to 0
before operating the motor. However, if
P3900 = 1 is set after commissioning, this
is done automatically.
P0100 Operation for Europe/ N. America
0 = Power in kW; f default 50 Hz
1 = Power in hp; f default 60 Hz
2 = Power in kW; f default 60 Hz
NOTE: DIP switches can permanently select
setting 0 or 1.
* P0304 Rated Motor Voltage
10 - 2000V
Rated motor voltage (V) from motor nameplate.
* P0307 Rated Motor Power
0.01 - 2000 kW or hp
Rated motor power (kW or hp) from motor
nameplate. If P0100 = 1, values will be in hp.
P1120 Ramp-up Time
0 - 650s
Time taken for the motor to accelerate from
standstill up to the maximum motor frequency.
P1082 Maximum Motor Frequency
Maximum motor frequency (0 - 650 Hz)
at which the motor will run irrespective of
the frequency setpoint. This value applies to
both clockwise and counterclockwise rotation.
P1080 Minimum Motor Frequency
Minimum motor frequency (0 - 650 Hz)
at which the motor will run irrespective of
the frequency setpoint. This value applies to
both clockwise and counterclockwise rotation.
** P1000 Selection of Frequency Setpoint
(on/off/reverse)
0 = No Frequency Setpoint
1 = Motor Potentiometer Setpoint
2 = Analog Setpoint
6 = P1/N2 Communications
P3900 End Quick Commissioning
0 = No quick commissioning (factory setting).
1 = End quick commissioning with motor
calculation and resetting all other parameters
to the factory setting
(recommended without bypass).
2 = End quick commissioning with motor
calculation and with I/O reset.
3 = End quick commissioning with motor
calculation, but without I/O reset
(recommended with bypass option).
P1121 Ramp-down Time
0 - 650s
Time taken for the motor to decelerate from
the maximum motor frequency down to standstill.
Motor related parameters.
Parameters have two settings:
IN000 = AUTO
IN001 = HAND
*
**
User Setting
User Setting
User Setting
* P0305 Rated Motor Current
0.01 - 10000A
Rated motor current (A) from motor nameplate.
User Setting
User Setting
* P0310 Rated Motor Frequency
12 - 650 Hz
Rated motor frequency (Hz) from motor nameplate.
User Setting
* P0311 Rated Motor Speed
0 - 40000 1/min
Rated motor speed (rpm) from motor nameplate.
User Setting
** P0700 Selection of Command Source
(on/off/reverse)
0 = Factory Setting
1 = Basic Operator Panel
2 = Terminal/Digital Inputs
6 = P1/N2 Communications
User Setting
User Setting
User Setting
User Setting
User Setting
User Setting
User Setting
Recommended:
(Fan: 60-120s,
Pump: 10-20s)
(20-30% Max)
Recommended:
(Fan: 60-120s,
Pump: 10-20s)
* P0308 Rated motor cosPhi, or
P0309 Rated motor efficiency
0.000 to 1.000 (P0308) or 0.0 to 99.9 (P0309)
Rated motor motor cosPhi or motor efficiency from
motor nameplate. If P0100=0 or 2, P0308 displays;
if P0100=1, P0309 displays.
User Setting
P0640 Motor Overload Factor
10 - 400%
Limited to maximum inverter current or to 400%
of rated current (P0305), whichever is lower.
User Setting