P0780: Defines y1 of the output characteristics
(factory setting = 10).
Example:
The factory-set scaling is as follows:
P1: 0.0 % = 0 mA or 0V
P2: 100.0 % = 20 mA or 10V
Index:
P0777[0]: IN000=Analog output 1.
P0777[1]: IN001=Analog output 2.
P0781, Width of deadband for analog outputs
P0781 defines the DAC deadband for the
analog outputs.
Setting range: 0 to 20 mA, or 0 to10V
Factory setting: 0
Index:
P0781[0]: IN000=Analog output 1.
P0781[1]: IN001=Analog output 2.
ymax
y2
y1
x1
x2
%
V
mA
ymin
P761
10
20
-10
-20
Frequency Setpoint (P1000)
Default setting: Analog input terminal 3/2 (AIN+/AINā, 0 to 10V corresponds to 0 to 50/60 Hz).
Index:
P1000[0]: IN000 (AUTO)=1st command data set (CDS).
P1000[1]: IN001 (HAND)=2nd command data set (CDS).
Additional settings: See P1000 (in the Appendix A: Parameter Reference List section of this
document).
Selection of Command Source (P0700)
Possible settings for P0700:
0= Factory setting (BICO reset), resets all digital inputs to the factory settings
(possible only if Function of Digital Input 1 parameter P0701=99, Enable BICO
parameterization).
1= Operator panel BOP.
2= Control terminal bar (factory setting).
4= USS on BOP link, AOP.
5= USS on COM link.
6= CB on COM link.
Index:
P0700[0]: IN000 (AUTO)=1st command data set (CDS).
P0700[1]: IN001 (HAND)=2nd command data set (CDS).