Technical data

Chapter 7 – Troubleshooting
Siemens Building Technologies, Inc. 61
Error Cause Diagnosis/Remedy Reaction
F0012, SED2
temperature
signal lost
Wire breakage of the
SED2 temperature
sensor (heat sink).
Off2
F0015, Motor
temperature
signal lost
Breakage or short-
circuit of the motor
temperature sensor.
If a signal loss is
detected, temperature
monitoring switches to
monitoring the thermic
motor image.
Off2
F0020, 1 phase
for mains supply
missing
One of the 3 phases for
the mains supply
voltage is missing.
Check the wiring of the 3 phases at
the supply voltage input of the SED2.
Off2
F0021, ground
fault
The ground fault occurs
if the sum of the phase
currents is higher than
5% of the nominal
SED2 current.
NOTE: This error message
occurs on SED2 drives with three
current sensors; that is, for SED2
drives of frame sizes D to F.
Off2
F0022, Power
stack fault
The fault is caused by the
following events:
(1) dc link overcurrent =short
circuit of IGBT.
(2) short circuit of dc link chopper
(3) earth fault.
Frame sizes A to C = (1),(2),(3).
Frame sizes D to E = (1),(2).
Frame size F = (2).
Since all these faults are
assigned to one signal on the
power stack, it is not possible to
establish which one actually
occurred.
Off2
F0023, Fault at
SED2 output
The On-phase is
interrupted at the SED2
output.
Off2