Error Cause Diagnosis/Remedy Reaction
F0024, Rectifier
overtemperature
The ventilation is
inadequate.
The fan is inoperative.
The ambient
temperature is too high.
Check the following:
The fan must turn when the
SED2 is running.
The pulse frequency
(P1800) must be set to
default value 4 kHz.
F0030, Fan Fault
The fan no longer
works.
The fault cannot be masked while the
options module (BOP or AOP) is
connected.
Replace the fan.
Off2