Technical data

SED2 Operation & Maintenance Manual
64 Siemens Building Technologies, Inc.
Error Cause Diagnosis/Remedy Reaction
F0051,
Parameter
EEPROM fault
Read or write failure
while saving non-
volatile parameter
Reset SED2 to factory setting and re-
parameterize
Off2
F0052, Power
stack fault
Read failure for power
stack information or
invalid data.
Exchange SED2. Off2
F0053, I/O
EEPROM fault
Read failure for I/O
EEPROM information or
invalid data.
Check the data.
Exchange the I/O module.
Off2
F0054, Wrong
I/O print
I/O print is not
connected.
Wrong I/O print is
connected.
No ID found on I/O
print, no data.
Check data flow.
Exchange I/O module.
Off2
F0060, ASIC
timeout
Internal communication
error.
If error reappears, exchange SED2.
Contact customer service.
Off2
F0070, CB
setpoint fault
No setpoints from CB
(communications board)
during telegram off time.
Check communications module (CB)
and communications partner.
Off2
F0071, USS
(BOP link)
setpoint fault
No setpoints from USS
during telegram off time.
Check communications to data
transmission module.
Check USS master.
Off2
F0072, USS
(COM link)
setpoint fault
No setpoints from USS
during telegram off time
Check USS master. Off2
F0080, ADC
input signal lost
Broken wire at analog
input.
Signal level outside
defined limits.
Off2
F0085, External
fault
External fault triggered
via input terminals.
Disable input terminals for fault
trigger, or eliminate external fault.
Check if DIN is set to ON.
Off2
F0101, Stack
overflow
Software or processor
error.
Run self-test routines. Off2
F0221, PID
feedback below
min. value
PID feedback below
minimum value of
P2268, minimum value
for PID feedback.
Change value of P2268.
Adjust feedback amplification.
Off2
F0222
PID feedback above
maximum value.
PID feedback, maximum value of
P2267 (maximum value for PID
feedback).
Adjust feedback amplification.
Off2