Technical data

Chapter 7 – Troubleshooting
Siemens Building Technologies, Inc. 69
Error Cause Diagnosis and Remedy Reaction
A0921, DAC
parameters not
set properly
DAC parameters must
not be set to identical
values, as illogical
values would result.
Index 0: Parameter
settings for output
identical.
Index 1: Parameter
settings for input
identical.
Index 2: Parameter
settings for output do
not correspond to DAC
type.
--
A0922, No load
applied to SED2
No load is applied to the
SED2.
Some functions may not
work as under normal
load conditions.
--
A0923, Both
JOG left and
JOG right are
requested
Both JOG right and
JOG left have been
requested. This freezes
the RFG output
frequency at its current
value.
--
A0924, Belt
failure detected
Load conditions at the
motor indicate a belt
failure or mechanical
fault.
Check the following:
No breakage, seizure, or
obstruction of drive train.
Correct operation of external
speed sensor, if in use.
--