Technical data

SED2 Operation & Maintenance Manual
84 Siemens Building Technologies, Inc.
Table 8. Point Database for Application 2722.
Point
Number
Point
Type
Descriptor
Factory
Default
(SI Units)
Engr.
Units
(SI
Units)
Slope
(SI
Units)
Intercept
(SI Units)
On Text
Off
Text
{26} LDI CONTROL
MODE
SERIAL - 1 0 SERIAL LOCAL
{27} LDI ENABLED OFF - 1 0 ENABLED OFF
{28} LDI READY TO
RUN
OFF - 1 0 READY OFF
{29} LDO DAY.NIGHT DAY - 1 0 NIGHT DAY
30 LAO CURRENT
LIM
1400 PCT .1 10 - -
31 LAO ACCEL TIME
1
500 SEC .02 0 - -
32 LAO DECEL TIME
1
500 SEC .02 0 - -
34 LDO SEL
HND.AUTO
AUTO - 1 0 AUTO HAND
{35} LDO RUN ENABLE ENABLE - 1 0 ENABLE OFF
40 LDO DIGITAL OUT
1
OFF - 1 0 ON OFF
41 LDO DIGITAL OUT
2
OFF - 1 0 ON OFF
{45} LAI ANALOG IN 1 0 PCT .1 -300 - -
{46} LAI ANALOG IN 2 0 PCT .1 -300 - -
{47} LAI ANALOG OUT
1
0 PCT .1 -100 - -
{48} LAI ANALOG OUT
2
0 PCT .1 -100 - -
{51} LAO FREQ REF 0 PCT 0.0061 0 - -
{52} LA1 FREQ
ACTUAL
0 PCT 0.0122 -100 - -
53 LAO FREQ MAX 2450 HZ 0.02 1 - -
{55} LAO PID SETP
REF
8602 PCT 0.0244 -200 - -
{56} LAI PID SETP
OUT
0 PCT 0.0122 -100 - -
57 LAO PID UP LMT 12288 PCT 0.0244 -200 - -
58 LAO PID LO LMT 8192 PCT 0.0244 -200 - -
{59} LAI PID OUTPUT 0 PCT 0.0122 -100 - -
{60} LAI PI FEEDBACK 0 PCT 0.0122 -100 - -