Technical data

Chapter 9 – Communications
Siemens Building Technologies, Inc. 85
Table 8. Point Database for Application 2722.
Point
Number
Point
Type
Descriptor
Factory
Default
(SI Units)
Engr.
Units
(SI
Units)
Slope
(SI
Units)
Intercept
(SI Units)
On Text
Off
Text
61 LAI P GAIN 0 PCT 0.002 0 - -
62 LAI I GAIN 0 PCT 2 0 - -
63 LAI D GAIN 0 PCT 2 0 - -
64 LDO ENABLE PID 0 - 1 0 ON OFF
66 LAI FEEDBK GAIN 0 PCT 0.02 0 - -
68 LAI LOW PASS 0 0.01 0 - -
{71} LDI DIGITAL IN 1 0 - 1 0 ON OFF
{72} LDI DIGITAL IN 2 0 - 1 0 ON OFF
{73} LDI DIGITAL IN 3 0 - 1 0 ON OFF
{74} LDI DIGITAL IN 4 0 - 1 0 ON OFF
{75} LDI DIGITAL IN 5 0 - 1 0 ON OFF
{76} LDI DIGITAL IN 6 0 - 1 0 ON OFF
80 LAO WDOG TIME 0 10 0 - -
83 LAI INVERTER
VER
0 - 0.01 0 - -
84 LAI DRIVE
MODEL
0 - 1 0 - -
{90} LAI LAST FAULT 0 - 1 0 - -
{91} LAI 1ST FAULT 0 - 1 0 - -
{92} LAI 2ST FAULT 0 - 1 0 - -
{93} LAI 3ST FAULT 0 - 1 0 - -
{94} LDI OKFAULT 0 - 1 0 FAULT OK
{95} LDO FAULT ACK 0 - 1 0 ON OFF
{96} LDI WARNING 0 - 1 0 WARN OK
{97} LAI LAST
WARNING
0 - 1 0 - -
{99} LAO ERROR
STATUS
0 - 1 0 - -
1. Points not listed are not used in this application.
2. A single value in a column means that the value is the same in English units and in SI
units.
3. Point numbers that appear in brackets { } may be unbundled at the field panel.