Technical data

SED2 Operation & Maintenance Manual
86 Siemens Building Technologies, Inc.
Table 9. Point Cross Reference to the SED2 Drive.
Point Number Descriptor Parameter
01 CTLR ADDRESS SBT
02 APPLICATION SBT
03 FREQ OUTPUT r0021
05 SPEED Calculated based on P0311
06 CURRENT roo27
07 TORQUE r0031
08 ACTUAL POWER r0032
09 TOTAL KWH r0039
13 DC BUS VOLT r0026
14 REFERENCE r0020
16 RATED PWR P0307
17 OUTPUT VOLTS r0025
21 FWD.REV r0054 bit 11
22 CMD FWD.REV P0842(2)
23 STOP.RUN r0019 bit 1
24 CMD STP.STRT P0840(2)
26 CONTROL MODE P0700(2)
27 ENABLED r0052 bit 0
28 READY TO RUN r0052 bit 1
29 DAY.NIGHT SBT
30 CURRENT LIM r0067
31 ACCEL TIME 1 read P1120
32 DECEL TIME 1 read P1121
34 SEL HND.AUTO(reference) P1000(2)
35 RUN ENABLE r0052 bit 0
40 DIGITAL OUT 1 P0731(2) read at r0747
41 DIGITAL OUT 2 P0732(2) read at r0747
45 ANALOG IN 1 r754(0)
46 ANALOG IN 2 r754(1)
51 FREQ REF r754(0)
52 FREQ ACTUAL r0754(0)
53 FREQ MAX P1082
55 PID SETP REF r754(0)